POLYPROPYLENE INSTALLATIONS
The  water  heater  has  been  approved  to  be  installed  with 
Polypropylene vent material as shown in Table 5 and Table 6. The 
approved  application  of  single  wall,  non-flexible,  non-concentric 
Polypropylene vent material is offered by two specific manufacturers 
(Centrotherm ECO Systems and DuraVent Polypropylene. These 
listed products must be installed by following the vent manufacturer’s 
instructions. Refer to “Table 7” on Page 27 to determine the maximum 
pipe length and number of elbows that can be used.
Insulation should not be used on Polypropylene venting materials. 
The use of insulation will cause increased vent wall temperatures, 
which could result in vent pipe failure.
Use only the adapters and vent system listed in Tables below. DO 
NOT mix vent systems of different types or manufacturers. Failure 
to comply could result in severe personal injury, death, or substantial 
property damage.
Installations must comply with applicable national, state, and local 
codes. If Polypropylene vent is not required by your local code, you 
may use either PVC or CPVC pipes for your water heater that allows 
non-metallic venting material installations.
Table 5
M & G Duravent PolyPro
Nominal Pipe 
Diameter
Flue Outlet Adapter
Adapter 
Connector
Ring 
Connector
90 Degree 
Elbow
Vent Material
Terminal(s)
2”
2PPS-AD
PPS-PAC
2PPS-LB
2PPS-E90
2PPS
2PPS & 2PPS-BG for Exhaust;
2PPS-E90 & 2PPS-BG for Intake (Direct Vent 
only)
3”
3PPS-AD
PPS-PAC
3PPS-LB
3PPS-E90
3PPS
3PPS & 3PPS-BG for Exhaust;
3PPS-E90 & 3PPS-BG for Intake (Direct Vent 
only)
Polypropylene vent systems do not use cement to connect the pipe 
and elbow sections but use a push together gasket seal method. 
Do not attempt to connect Polypropylene with sealant cement. All 
vent connections MUST be secured by the vent manufacturer’s joint 
connector. The installer must use a specific vent starter adapter at 
the flue connection. The adapter is supplied by the vent manufacturer 
to adapt to its vent system.
In order to be in full compliance with UL 1738 or ULC-S636 and to 
meet the requirements of the water heater manufacturer, you must 
use the metal joint connector rings, available from the Polypropylene 
vent manufacturer, to stiffen the joints of 2”, and 3” diameter pipes.
Table 6
Centrotherm InnoFlue SW
Nominal Pipe 
Diameter
Flue Outlet Adapter
Adapter 
Connector
Ring 
Connector
90 Degree 
Elbow
Vent Material
Terminal(s)
2”
ISAGL 
0202
IAFC02
IANS02
ISELL0287
ISVL02
ISVL02 & IASPP02 for Exhaust;
ISELL0287 & IASPP02 for Intake (Direct Vent 
only)
3”
ISAGL 
0303
IAFC03
IANS03
ISELL0387
ISVL03
ISVL03 & IASPP03 for Exhaust;
ISELL0387 & IASPP03 for Intake (Direct Vent 
only)