LOW PROFILE TERMINATION INSTALLATION
This  water  heater  is  certified  for  sidewall  direct  venting  with  IPEX 
System 636 Low Profile Vent Kit. Follow instructions below for proper 
installations.
All termination kits must be located and installed in accordance with 
local codes or the current editions of the National Fuel Gas Code 
(ANSI Z223.1/NFPA 54).
1.  Once the proper location has been determined, cut 2 holes in the 
wall large enough to accomodate the pipe. Pipe diameters and 
distance between hole centers can be found in Table 9.
2. Slide both the intake and exhaust pipes through the holes. Solvent 
cement both pipes to the base of the vent termination kit, follow the 
solvent cementing procedures outlined in the IPEX System 636 
Installation Guide, which is available on the web www.ipexinc.com.
3. To fasten the Base to the wall, use the supplied screws and anchors. 
A 3/16” (5mm) hole, 1-3/16” (30mm) deep, will need to be drilled for 
the anchors. Locate the anchor hole using the base as a template.
4. Screw the Cap to the Base using the supplied screws.
5.  Once  the  vent  termination  and  pipes  are  secured,  the  wall 
penetrations will need to be sealed from the interior using a PVC-
compatible sealant material.
6. All vent pipes and air inlets must terminate at the same height to 
avoid possibility of severe personal injury, death, or substantial 
property damage.
8.  Operate heater through 1 heat cycle to ensure combustion-air and 
vent pipes are properly connected to concentric vent termination 
connections.
Figure: 32
Vent Base
Vent Cap
Air Piping
Vent Piping
Table 9
Low Profile Termination Kits - Dimensions
AOS Kit 
Number
IPEX Part 
Number
Description
Pipe Outside  
Diameter
Hole Spacing  
(ctr to ctr)
327479-000
196984
2” Flush Mount Vent Kit
2.375”
5.6”
327478-000
196985
3” Flush Mount Vent Kit
3.5”
5.6”
Table 10
Each Kit Contains
Qty
Item Description
1
Base (two holes)
1
Cap (one hole)
8
Stainless Steek Screws
4
Plastic Anchors
To Boiler Intake 
Air Connection
From Boiler Vent 
Pipe Connection
Vent/Air 
Termination
12” 
Min to 
Over-
Hang
12” 
Min
Grade or 
Snow Line
Possible Orientations
12” Min between Edge of Air 
Inlet and Adjacent Vent Outlet
Air
Vent/Air 
Termination
Vent
Figure: 33
Figure: 34