ELECTRONIC CONTROL SYSTEM
Servicing should only be performed by a Qualified Service Agent
50
Table 1 Status Icons
ICON
DESCRIPTION
Water temperature in the tank has fallen. Shaded area of the animated thermometer icon 
will rise and fall in response to water temperature in the storage tank as sensed from the 
immersion Temperature Probe.
Water temperature in the tank has reached the Operating Set Point. Shaded area of the 
animated thermometer icon will rise and fall in response to water temperature in the 
storage tank as sensed from the immersion Temperature Probe.
The control is unable to initiate a heating cycle. This will happen whenever a Fault 
condition is detected by the control system or when either of the two Enable/Disable 
circuits are open circuits. For more information on Enable/Disable circuits see page 45 
and the Heater Status Menu information on page 54.
The control system is in Heating Mode and has energized the electromagnetic contactor 
coils for at least one bank of heating elements. This animated icon DOES NOT indicate 
current has been sensed from the heating elements, only that there is a call for heat 
present and the control system has initiated heating element operation.
Heating elements icon for a water heater equipped with 1 Bank of heating elements. 
Each circle represents one heating element. Each diagonal row of 3 elements = 1 Bank 
of elements. Open circles represent heating elements the control system has not 
energized and is not sensing electrical current from.
Heating elements icon for a water heater equipped with 2 Banks of heating elements. 
Each circle represents one heating element. Each diagonal row of 3 elements = 1 Bank 
of elements. Open circles represent heating elements the control system has not 
energized and is not sensing electrical current from.
Heating elements icon for a water heater equipped with 3 Banks of heating elements. 
Each circle represents one heating element. Each diagonal row of 3 elements = 1 Bank 
of elements. Open circles represent heating elements the control system has not 
energized and is not sensing electrical current from.
Heating elements icon for a water heater equipped with 3 Banks of heating elements. 
Each circle represents one heating element. Each diagonal row of 3 elements = 1 Bank 
of elements. Filled circles represent heating elements the control system has energized 
AND is sensing electrical current from.
Heating elements icon for a water heater equipped with 3 Banks of heating elements. 
Each circle represents one heating element. Each diagonal row of 3 elements = 1 Bank 
of elements. Open circles with an X represent heating elements the control system has 
energized that it IS NOT sensing electrical current from.
Heating elements icon for a water heater equipped with 3 Banks of heating elements. In 
this example 2 Banks (6 elements) have been energized and 3 elements have not. The 
control system is sensing electrical current from 4 heating elements. The control system 
is reporting that it is not sensing electrical current from 2 elements that it should be 
sensing current from. The control system would declare an Alert Condition in this case.
The control has detected/declared a Fault Condition. Fault message details can be 
viewed in the Current Fault menu. Heating operation is discontinued (locked out) until 
the condition that caused the fault is corrected. Power to the water heater must be cycled 
off and on to reset the control system. Note; cycling power will not reset the control 
system if the condition that caused the fault has not been corrected.
The control has detected/declared an Alert Condition. The water heater will continue to 
operate during an Alert Condition but there is an operational condition that requires the 
attention of a Qualified Service Agent. Alert message details can be viewed in the 
Current Alert menu.