the bottom of the unit (see figure 12). Condensate from this water 
heater is mildly acidic. Please note that some local codes require 
that condensate is treated by using a pH neutralizing filter prior to 
disposal.
Caution must be used to ensure that the drain is free and clear of 
debris and will not allow backflow through the condensate hose. 
Consideration must be given to avoid freezing of the condensate 
lines which could  result in excessive build up of condensate inside 
the  water  heater.  Waterproof  heat  tape  may  be  required  to  prevent 
freezing of the condensate lines. Please ensure that the outlet of the 
condensate drain does not create a slippery condition which could 
lead to personal injury.
CONDENSATION  WARNING:  THIS  WATER  HEATER  IS  A 
CONDENSING UNIT AND REqUIRES A DRAIN TO BE LOCATED 
IN CLOSE PROXIMITY TO ALLOW CONDENSATE TO DRAIN 
SAFELY. THE CONDENSATE DRAINS FROM UNIT AT THE 
EXHAUST  ELBOW  LOCATED  AT  BOTTOM  OF  UNIT.  NOTE: 
IT IS IMPORTANT THAT THE CONDENSATE HOSE NOT BE 
ELEvATED ABOvE THE EXHAUST ELBOW, SEE FIGURE 12. 
CONDENSATE BUILD-UP WILL BLOCk THE EXHAUST OUTLET, 
WHICH WILL CAUSE IMPROPER OPERATION.
fIGure 12.
the condensate drain line must be routed to a suitable drain. If 
no floor drain is available or the drain is above the level of the 
condensate line, install a condensate pump that is resistant 
to the acidic condensate. these pumps are available from 
local distributors. If the pump is not resistant to acidic water, 
a condensate neutralizer must be used ahead of the pump. 
when installing the drain line, note the following:
•  Plastic pipe or tubing must be used to connect the condensate 
drain  to  a  suitable  drain  or  condensate  pump.  Do  not  use 
copper tubing, iron, or steel pipe for the condensate drain line.
•  Condensate  drain  lines  should  be  installed  in  conditioned 
areas  only.  Drain  lines  installed  in  areas  that  are  subject  to 
freezing  temperatures  should  be  wrapped  with  a  nationally 
recognized/listed  heat  tape  and/or  approved  insulation  for 
freeze protection. Install per manufacturer’s instructions.
•  Do  not  common  drain  with  the  temperature  and  pressure  relief 
valve or the condensate line from an air conditioner evaporator coil.
•  Slope  the  condensate  drain  toward  the  inside  floor  drain  or 
condensate pump.
•  The condensate drain line and connection to the drain piping 
must comply with all local codes.
hIGh altItude InstallatIons
This  high  efficiency  water  heater  is  certified  for  use  without 
modification for an altitude of 10,000 feet (3,079 meters). Consult 
the factory for installation at altitudes over 10,100 feet (3,079m).
Some  gas  utility  companies  derate  their  gas  for  altitude,  making 
it unnecessary to install high altitude orifices. Call the local gas or 
utility company to verify BTU content.
Due to the input ration reduction at high altitudes, the output rating 
of the appliance is also reduced and should be compensated for in 
the sizing of the equipment for applications.
fIllInG the water heater
Never  use  this  water  heater  unless  it  is  completely  full  of  water. 
To prevent damage to the tank, the tank must be filled with water. 
Water must flow from the hot water faucet before turning “ON” gas 
to the water heater.
To fill the water heater with water:
1.  Close the water heater drain valve by turning the handle to the 
right (clockwise). The drain valve is on the lower front of the water 
heater.
2.  Open  the  cold  water  supply  valve  to  the  water  heater.  
 
note: the cold water supply valve must be left open when 
the water heater is in use.
3.  To insure complete filling of the tank, allow air to exit by opening 
the nearest hot water faucet.  Allow water to run until a constant 
flow is obtained. This will let air out of the water heater and the 
piping.
4.  Check  all  water  piping  and  connections  for  leaks.  Repair  as 
needed.