Minimum  clearances  between  the  water  heater  and  combustible 
construction  are  0  inch  at  the  sides  and  rear,  5.5”  (14.0  cm)  from 
the front and 18” (45.7 cm) from the top. (Standard clearance.) If 
clearances stated on the heater differ from standard clearances, install 
water heater according to clearances stated on the heater.
Adequate clearance 30” (76 cm) for servicing this water heater should 
be considered before installation, such as changing the anode rods, 
control system components and gas control valve.
A minimum clearance of 5.5” (14.0 cm) must be allowed for access to 
replaceable and/or serviceable parts such as the thermostats, drain valve, 
condensate drain, temperature-pressure relief valve, clean out opening, 
and the vent connection (exhaust elbow).
When installing the heater, consideration must be given to proper 
location. Location selected should be as close to the wall as practicable 
and as centralized with the water piping system as possible.
Figure 3: CLEARANCES
INSULATION BLANKETS
Insulation blankets are available to the general public for external use 
on gas water heaters but are not necessary with these products. The 
purpose of an insulation blanket is to reduce the standby heat loss 
encountered with storage tank heaters. Your water heater meets or 
exceeds the Energy Policy Act standards with respect to insulation and 
standby loss requirements, making an insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this heater, you 
should follow these instructions (For identification of components 
75 GALLON UNIT”. Failure to follow these instructions can restrict 
the air flow required for proper combustion, potentially resulting in 
fire, asphyxiation, serious personal injury or death.
•  Do not apply insulation to the top of the water heater, as this will  
interfere with safe operation of the blower assembly.
•  Do not cover the control system LCD on top of the water heater.
•  Do not cover the outer door, thermostat or temperature & pressure  
relief valve.
• Do not cover the instruction manual. Keep it on the side of the  
water heater or nearby for future reference.
• Do obtain new warning and instruction labels from the manufacturer  
for placement on the blanket directly over the existing labels.
• Do inspect the insulation blanket frequently to make certain it does 
not sag, thereby obstructing combustion air flow.
COMBUSTION AIR AND VENTILATION
A  gas  water  heater  cannot  operate  properly  without  the  correct 
amount of air for combustion. Do not install in a confined area such 
as a closet, unless you provide air as shown in the Facts to Consider 
About Location section. Never obstruct the flow of ventilation air. If 
you have any doubts or questions at all, call your gas supplier. Failure 
to provide the proper amount of combustion air can result in a fire or 
explosion and cause death, serious bodily injury, or property damage.
Figure 4: COMBUSTION AIR AND VENTILATION
If  this  water  heater  will  be  used  in  beauty  shops,  barber  shops, 
cleaning establishments, or self-service laundries with dry cleaning 
equipment,  it  is  imperative  that  the  water  heater(s)  be  installed 
direct  vent  so  that  all  air  for  combustion  and  ventilation  is  taken 
from outdoors. 
Propellants of aerosol sprays and volatile compounds, (cleaners, 
chlorine  based  chemicals,  refrigerants,  etc.)  in  addition  to  being 
highly flammable in many cases, will also react to form corrosive 
hydrochloric  acid  when  exposed  to  the  combustion  products  of 
the water heater. The results can be hazardous, and also cause 
product failure.