VENT INSTALLATION CONSIDERATIONS
This  water  heater  can  be  vented  using  room  air  for  intake 
combustion air, or direct vented so that all intake air for combustion 
comes from the outside through a sealed pipe.
This  water  heater  may  be  installed  in  4  separate  orientations 
depending  on  the  requirements  of  the  building  and  the  water 
heater. The installer must decide which method is most appropriate 
for each installation. These orientations are:
1.  Vertical  Termination  -  vertical  vent  termination  through 
unenclosed or enclosed areas with roof penetration, refer to 
Vertical Vent Terminal Installation on Page 31.
2.  Through-the-Wall  Termination  -  horizontal  vent  termination 
directly  through  an  outside  wall,  see  “Figure  12:  VENT 
3.  Horizontal Direct Vent - using Through-the-Wall Termination to 
exhaust flue products and piping to bring combustion air to the 
4.  Vertical  Direct  Vent  -  using  a  vertical  vent  termination  to 
exhaust  flue  products  and  piping  to  bring  combustion  air  to 
the water heater from outside, see “Figure: 20” “Figure: 21” 
on Page 32.
In cold climates any water vapor remaining in the flue gases will 
condense into a cloud of vapor at the point where the vent system 
exits the building. Special consideration is recommended, before 
locating the vent termination near walkways, windows and building 
entrances.
 
Direct  venting  into  dead  spaces  such  as  alleys,  atriums,  and 
inside corners can cause recirculation of flue gases. Recirculation 
of flue gases will cause sooting, and icing of the combustion air 
intake  during  severe  cold  weather.  To  prevent  the  recirculation 
of  flue  gases,  maintain  as  much  distance  as  possible  between 
the  combustion  air  intake  and  the  exhaust  vent  terminal  refer  to 
NOTE:  This  unit  can  be  vented  with  PVC  pipe  materials  (DWV 
ASTM-D2665 or CSA B181.2; Schedule 40, 80, 120 ASTM-D1785 
or  CSA  B137.3;  or  SDR  Series  ASTM-D2241  or  CSA  B137.3), 
CPVC  pipe  materials  (CPVC41  ASTM-D2846  or  CSA  B137.6; 
Schedule  40,  80  ASTM-F441  or  CSA  B137.6;  or  SDR  Series 
ASTM-F442), ABS pipe materials (Schedule 40 DWV ASTM-D2661 
or  CSA  B181.1)  and  Centrotherm  ECO  Systems  and  DuraVent 
Polypropylene  listed  vent  systems.  The  fittings,  other  than  the 
TERMINATION should be equivalent to PVC-DWV fittings meeting 
ASTM D-2665 (Use CPVC fittings, ASTM F-438 for CPVC pipe and 
ABS fittings, ASTM D-2661/3311 for ABS pipe). If CPVC or ABS 
pipe and fittings are used, then proper cement must be used for all 
joints, including joining the pipe to Termination (PVC Material). If 
Polypropylene pipe and fittings are used, the metal joint connector 
rings, available from the Polypropylene vent manufacturer must be 
used to stiffen the joints of pipes.
PVC  Materials  should  use ASTM  D-2564  Grade  Cement;  CPVC 
Materials  should  use  ASTM  F-493  Grade  Cement  and  ABS 
Materials should use ASTM D-2235 Grade Cement.
If  the  water  heater  is  being  installed  as  a  replacement  for  an 
existing  power  vented  heater  in  pre-existing  venting,  a  thorough 
inspection  of  existing  venting  system  must  be  performed  prior 
to  any  installation  work.  Verify  that  correct  material  as  detailed 
above  has  been  used,  and  that  the  minimum  or  maximum  vent 
lengths and terminal location as detailed in this manual have been 
met. Carefully inspect the entire venting system for any signs of 
cracks or fractures, particularly at joints between elbows and other 
fittings and straight runs of vent pipe. Check system for signs of 
sagging or other stresses in joints as a result of misalignment of 
any components in the system. If any of these conditions are found, 
they must be corrected in accordance with the venting instructions 
in this manual before completing installation and putting the water 
heater into service.
NOTE:  For  water  heaters  in  locations  with  high  ambient 
temperatures above 100°F (38°C) it is recommended that CPVC or 
Polypropylene or ABS pipe and fittings be used.
All vent (exhaust) pipes must be pitched a minimum of a 1/4” per 
foot back to the water heater to allow drainage of condensation. 
Never operate the water heater unless it is vented to the outdoors.
The  instructions  in  this  section  of  the  manual  must  be  followed 
to avoid choked combustion or recirculation of flue gases. Such 
conditions cause sooting of the combustion chamber, burners and 
flue tubes and creates a risk of asphyxiation.
For direct vent application where combustion air might be supplied 
from  extremely  cold  ambient  through  fresh  air  intake  piping 
system, it is recommended that a backflow preventer be installed 
at the intake vent terminal close to the blower before proceeding 
with installation of the rest of the fresh air intake piping. Call the 
technical support phone number listed on the back cover of this 
manual for more information.