UNCONFINED SPACE
An Unconfined Space is one whose volume IS NOT LESS THAN 
50  cubic  feet  per  1,000  Btu/hr  (4.8  cubic  meters  per  kW)  of  the 
total  input  rating  of  all  appliances  installed  in  the  space.  Rooms 
communicating directly with the space, in which the appliances are 
installed, through openings not furnished with doors, are considered 
a part of the unconfined space.
Makeup air requirements for the operation of exhaust fans, kitchen 
ventilation  systems,  clothes  dryers  and  fireplaces  shall  also  be 
considered  in  determining  the  adequacy  of  a  space  to  provide 
combustion, ventilation and dilution air.
UNUSUALLY TIGHT CONSTRUCTION
In unconfined spaces in buildings, infiltration may be adequate to 
provide air for combustion, ventilation and dilution of flue gases. 
However, in buildings of unusually tight construction (for example, 
weather  stripping,  heavily  insulated,  caulked,  vapor  barrier,  etc.) 
additional air must be provided using the methods described in the 
Confined Space section that follows.
CONFINED SPACE
A Confined Space is one whose volume IS LESS THAN 50 cubic 
feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input 
rating of all appliances installed in the space.
Openings  must  be  installed  to  provide  fresh  air  for  combustion, 
ventilation and dilution in confined spaces. The required size for 
the openings is dependent on the method used to provide fresh 
air  to  the  confined  space AND  the  total  Btu/hr  input  rating  of  all 
appliances installed in the space.
DIRECT VENT APPLIANCES
Appliances  installed  in  a Direct  Vent configuration  that derive  all 
air  for  combustion  from  the  outdoor  atmosphere  through  sealed 
intake air piping are not factored in the total appliance input Btu/hr 
calculations used to determine the size of openings providing fresh 
air into confined spaces.
EXHAUST FANS
Where exhaust fans are installed, additional air shall be provided 
to replace the exhausted air. When an exhaust fan is installed in 
the same space with a water heater, sufficient openings to provide 
fresh  air  must  be  provided  that  accommodate  the  requirements 
for  all  appliances  in  the  room  and  the  exhaust  fan.  Undersized 
openings will cause air to be drawn into the room through the water 
heater’s  vent  system  causing  poor  combustion.  Sooting,  serious 
damage to the water heater and the risk of fire or explosion may 
result. It can also create a risk of asphyxiation.
LOUVERS AND GRILLES
The  free  areas  of  the  fresh  air  openings  in  the  instructions  that 
follow do not take in to account the presence of louvers, grilles or 
screens in the openings.
The  required  size  of  openings  for  combustion,  ventilation  and 
dilution air shall be based on the net free area of each opening. 
Where the free area through a design of louver or grille or screen is 
known, it shall be used in calculating the size of opening required to 
provide the free area specified. Where the louver and grille design 
and free area are not known, it shall be assumed that wood louvers 
will have 25% free area and metal louvers and grilles will have 75% 
free area. Non motorized louvers and grilles shall be fixed in the 
open position.
FRESH AIR OPENINGS FOR CONFINED SPACES
The following instructions shall be used to calculate the size, number 
and  placement  of  openings  providing  fresh  air  for  combustion, 
ventilation and dilution in confined spaces. The illustrations shown 
in  this  section  of  the  manual  are  a  reference  for  the  openings 
that provide fresh air into confined spaces only. 
DO NOT refer to 
these illustrations for the purpose of vent installation. See Venting 
Installation on Page 25 for complete venting installation instructions.
OUTDOOR AIR THROUGH TWO OPENINGS
Figure: 5
The  confined  space  shall  be  provided  with  two  permanent 
openings, one commencing within 12 inches (300 mm) of the top 
and one commencing within 12 inches (300 mm) of the bottom of 
the enclosure. The openings shall communicate directly with the 
outdoors. See Figure 5.
Each opening shall have a minimum free area of 1 square inch per 
4,000 Btu/hr (550 mm
2
 per kW) of the aggregate input rating of all 
appliances  installed in the enclosure.  Each opening  shall  not be 
less than 100 square inches (645 cm
2
).
OUTDOOR AIR THROUGH ONE OPENING
Figure: 6