American Water Heater VG6250T 110 Benutzerhandbuch

Seite von 60
20
GAS SUPPLY SYSTEMS
Low  pressure  building  gas  supply  systems  are  defined  as  those 
systems that cannot under any circumstances exceed 14” W.C. (1/2 
PSI  Gauge).  These  systems  do  not  require  pressure  regulation. 
Measurements  should  be  taken  to  insure  that  gas  pressures  are 
stable and fall within the requirements stated on the water heater 
rating plate. Readings should be taken with all gas burning equipment 
off (static pressure) and with all gas burning equipment running at 
maximum rate (dynamic pressure). The gas supply pressure must 
be stable within 1.5” W.C. from static to dynamic pressure to provide 
good performance. Pressure drops that exceed 1.5” W.C. may cause 
rough starting, noisy combustion or nuisance outages. Increases or 
spikes in static pressure during off cycles may cause failure to ignite 
or  in  severe  cases  damage  to  water  heater  gas  control  valves.  If 
your low pressure system does NOT meet these requirements, the 
installer is responsible for the corrections.
High Pressure building supply systems use pressures that exceed 
14” W.C. (1/2 PSI Gauge). These systems must use field supplied 
regulators to lower the gas pressure to less than 14” W.C. (1/2 PSI 
Gauge). Appliances  require  gas  regulators  that  are  properly  sized 
for  the  water  heater  input  and  deliver  the  rating  plate  specified 
pressures. Gas supply systems where pressure exceeds 5 PSI often 
require multiple regulators to achieve desired pressures. Systems in 
excess of 5 PSI building pressure should be designed by gas delivery 
professionals for best performance. Water heaters connected to gas 
supply systems that exceed 14” W.C. (1/2 PSI Gauge) at any time 
must be equipped with a gas supply regulator. 
GAS PRESSURE REQUIREMENTS
All models require a minimum gas supply pressure of 3.5” W.C.(0.87 
kPa)  for  natural  gas  and  8.0”  W.C.  (1.99  kPa)  for  propane.  The 
minimum  supply  pressure  is  measured  while  gas  is  not  flowing 
(static pressure) AND while gas is flowing (dynamic pressure). The 
supply  pressure  (static  and  dynamic)  should  never  fall  below  3.5” 
W.C.(0.87 kPa) for natural gas or 8.0” W.C. (1.99 kPa) for propane. 
The  supply  pressure  should  be  measured  with  all  gas  fired  water 
heaters connected to the common main firing at full capacity. If the 
supply pressure drops more than 1.5” W.C. (0.37 kPa) as gas begins 
to flow to the water heater then the supply gas system including the 
gas line and/or the gas regulator may be restricted or undersized. 
See Supply Gas Regulator section and Gas Piping section of this 
manual. The gas control valve on all models has a maximum gas 
supply  pressure  limit  of  14”  W.C.(3.48  kPa) The  maximum  supply 
pressure is measured while gas is not flowing (static pressure) AND 
while gas is flowing (dynamic pressure).
SUPPLY GAS REGULATOR
The maximum allowable gas supply pressure for this water heater 
is 14 inches W.C. (3.5 kPa). Install a positive lock-up gas pressure 
regulator in the gas supply line if inlet gas pressure can exceed 14 
inches W.C. (3.5 kPa) at any time. Regulators must be sized/used 
according to manufacturer’s specifications.
If a positive lock-up regulator is required follow these instructions:
1. Positive lock-up gas pressure regulators must be rated at or above 
the input Btu/hr rating of the water heater they supply.
2. Positive lock-up gas pressure regulator(s) should be installed no 
closer than 3 feet (1 meter) and no farther than 8 feet (2.4 meters) 
from the water heater’s inlet gas connection.
3. After installing the positive lock-up gas pressure regulator(s) an 
initial nominal supply pressure setting of 7.0” W.C.(1.74 kPa) for 
Natural  Gas  and  11.0”  W.C.  (2.74  kPa)  for  Propane  (LP)  while 
the water heater is operating is recommended and will generally 
provide good water heater operation. Some additional adjustment 
may be required later to maintain a steady gas supply pressure. 
4. When  installing  multiple  water  heaters  in  the  same  gas  supply 
system  it  is  recommended  that  individual  positive  lock-up  gas 
pressure regulators be installed at each unit.
All gas piping must comply with local codes and ordinances or with 
the current editions National Fuel Gas Code (ANSI Z223.1/ NFPA-
54).  Copper  or  brass  tubing  and  fittings  (except  tin  lined  copper 
tubing) shall not be used.
If the gas control valve is subjected to pressures exceeding 1/2 psi 
(3.5 kPa), the damage to the gas control valve could result in a fire 
or explosion from leaking gas.
If the main gas line Shut-off serving all gas water heaters is used, 
also turn off the gas at each water heater. Leave all gas appliances 
shut off until the water heater installation is complete.
A gas line of sufficient size must be run to the water heater. Consult 
the current edition of National Fuel Gas Code (ANSI Z223.1/NFPA 
54) and your gas supplier concerning pipe size.
There must be:
•  A readily accessible manual shut off valve in the gas supply line 
serving the water heater, and
•  A sediment trap ahead of the gas control valve to help prevent dirt 
and foreign materials from entering the gas control valve.
•  A ground joint union of proper size between the manual shut off 
valve and control valve to permit servicing of the unit.
Be sure to check all the gas piping for leaks before lighting the water 
heater.  Use  a  soapy  water  solution,  not  a  match  or  open  flame. 
Rinse off soapy solution and wipe dry.