DIRECT VENT TERMINAL INSTALLATION
The air intake provided on the unit contains an air intake screen to 
prevent large particles from entering the unit.
Figure 13: AIR INTAKE SCREEN
When the unit is to be setup as a direct vent, the air intake screen 
must be removed. The air intake pipe may then be glued to the air 
intake (see Figure 13) provided on the unit.
This unit consists of two terminals - an air intake terminal and an 
exhaust vent terminal. The air intake terminal is a 2” 90° pvc elbow 
with an air intake screen and the exhaust vent terminal is a 2” straight 
pvc coupling with a mesh wire screen.
Note: to prevent exhausting products from circulating to the air intake 
in windy/cold areas, the maximum practical distance between these 
two terminals is recommended.
Figure: 13A
INSTALLATION SEQUENCE
1.  After  the  points  of  termination  have  been  determined, 
use  the  cover  plates  as  templates  to  mark  the  holes  for 
the vent pipes to be inserted through the wall. BEWARE OF 
CONCEALED WIRING AND PIPING INSIDE OF WALL. If the 
vent terminals are being installed on the outside of a finished 
wall,  it  may  be  easier  to  mark  both  the  inside  and  outside 
wall. Align the holesby drilling a hole through the center of the 
template from the inside through to the outside. The template 
can now be positioned on the outside wall using the drilled holes 
as a centering point for the template.
  A.)  MASONRY  SIDE  WALLS  Chisel  an  opening  approximately 
   1/2” (1.3 cm) larger than the marked circle.
    B.)  WOODEN SIDE WALLS Drill a pilot hole approximately 
     
one  quarter  inch  outside  of  the  marked  circle.  This 
     
pilot  hole  is  used  as  a  starting  point  for  a  saws-all  or 
     
sabre saw blade. Cut around the marked circle staying 
     
approximately  one  quarter  inch  outside  of  the  line. 
     
(This  will  allow  the  vent  pipe  to  easily  slide  through 
     
the  opening. The  resulting  gap  will  be  covered  by  the 
     
vent  terminal  cover  plates.)  Repeat  this  step  on  the 
     
inside wall if necessary.
2.  Cut  a  length  of  pipe  about  3.5”  (8.9  cm)  longer  than  the 
  wall thickness at the opening.
3.  Glue the air intake terminal to the section of the pipe.
4.  Slide the wall plate over pipe to stop against air intake terminal.
5.  Place a bead of caulking (not supplied) around the gap between 
  the  pipe  and  the  wall.  Place  some  of  the  caulking  on  the 
  back of the plate to hold it against the wall after installation.
6.  If the air intake pipe is installed up to the wall, with a coupling on the 
  end against the wall opening, the pipe with the air intake terminal can 
  be prepared for gluing before inserting through the wall. Slide the 
  pipe through the wall and insert into coupling on the other side of 
  the wall, making sure that the air intake terminal ends up pointed in the 
  correct position (Figure 13A and Figure 14).
Figure: 14
Air Intake Screen
Blower Air Inlet Assembly