HOT WATER
OUTLET
TO TANK
INLET
CHECK
VALVE
MIXING
VALVE
COLD
WATER
INLET
TEMPERED WATER
OUTLET
12” TO 15”
(30-38 cm)
CHECK
VALVE
figure 10
dishwashing machines
All  dishwashing  machines  meeting  the  National  Sanitation 
Foundation  requirements  are  designed  to  operate  with  water 
flow pressures between 15 and 25 pounds per square inch (103 
kPa and 173 kPa). Flow pressures above 25 pounds per square 
inch (173 kPa), or below 15 pounds per square inch (103 kPa), 
will result in improperly sanitized dishes. Where pressures are 
high, a water pressure reducing or flow regulating control valve 
should  be  used  in  the  180°F  (82°C)  line  to  the  dishwashing 
machine  and  should  be  adjusted  to  deliver  water  pressure 
between these limits.
The National Sanitation Foundation also recommends circulation 
of 180°F (82°C) water. Where this is done, the circulation should 
be  very  gentle  so  that  it  does  not  cause  any  unnecessary 
turbulence inside the water heater. The circulation should be just 
enough to provide 180°F (82°C) water at the point of take-off to 
the dishwashing machine.
Adjust  flow  by  throttling  a  full  port  ball  valve  installed  in  the 
circulating line on the outlet side of the pump. Never throttle flow 
on the suction side of a pump. See Water Piping Diagrams in 
this manual.
closed water systems
Water  supply  systems  may,  because  of  code  requirements 
or  such  conditions  as  high  line  pressure,  among  others,  have 
installed  devices  such  as  pressure  reducing  valves,  check 
valves, and back flow preventers. Devices such as these cause 
the water system to be a closed system.
thermal expansion
As water is heated, it expands (thermal expansion). In a closed 
system the volume of water will grow when it is heated. As the 
volume  of  water  grows  there  will  be  a  corresponding  increase 
in water pressure due to thermal expansion. Thermal expansion 
can cause premature tank failure (leakage). This type of failure 
is  not  covered  under  the  limited  warranty.  Thermal  expansion 
can also cause intermittent Temperature-Pressure relief Valve 
operation:  water  discharged  from  the  valve  due  to  excessive 
pressure build up. This condition is not covered under the limited 
warranty. The Temperature-Pressure relief Valve is not intended 
for the constant relief of thermal expansion.
A  properly  sized  thermal  expansion  tank  must  be  installed  on 
all  closed  systems  to  control  the  harmful  effects  of  thermal 
expansion. Contact a local plumbing service agency to have a 
thermal expansion tank installed.
See Water Line Connections on page 19 and the Water Piping 
Diagrams beginning on page 34.
temperature-pressure relief ValVe
Explosion Hazard
Temperature-Pressure Relief Valve
must comply with ANSI Z21.22-
CSA 4.4 and ASME code.
Properly sized temperature-
pressure relief valve must be
installed in opening provided.
Can result in overheating and
excessive tank pressure.
Can cause serious injury or death.
This  water  heater  is  provided  with  a  properly  rated/sized  and 
certified  combination  Temperature-Pressure  relief  Valve  (T&P 
valve) by the manufacturer. The valve is certified by a nationally 
recognized testing laboratory that maintains periodic inspection 
of  production  of  listed  equipment  of  materials  as  meeting  the 
requirements  for  relief  Valves  for  hot  Water  Supply  Systems, 
ANSI Z21.22 • CSA 4.4, and the code requirements of ASMe.
If  replaced,  the  new  T&P  valve  must  meet  the  requirements 
of  local  codes,  but  not  less  than  a  combination  Temperature-
Pressure  relief  Valve  rated/sized  and  certified  as  indicated  in 
the  above  paragraph.  The  new  valve  must  be  marked  with  a 
maximum  set  pressure  not  to  exceed  the  marked  hydrostatic 
working pressure of the water heater (150 psi = 1,035 kPa) and 
a discharge capacity not less than the water heater Btu/hr or kW 
input rate as shown on the water heater’s model rating label.
NOTe: In addition to the factory installed Temperature-Pressure 
relief Valve on the water heater, each remote storage tank that 
may be installed and piped to a water heating appliance must also 
have its own properly sized, rated and approved Temperature-
Pressure  relief  Valve  installed.  Call  the  toll  free  technical 
support phone number listed on the back cover of this manual 
for technical assistance in sizing a Temperature-Pressure relief 
Valve for remote storage tanks.
For safe operation of the water heater, the Temperature-Pressure 
relief Valve must not be removed from its designated opening 
nor  plugged.  The  Temperature-Pressure  relief  Valve  must  be 
installed directly into the fitting of the water heater designed for the 
relief valve. Install discharge piping so that any discharge will exit 
the pipe within 6 inches (15.2 cm) above an adequate floor drain, 
or external to the building. In cold climates it is recommended 
that it be terminated at an adequate drain inside the building. Be 
certain that no contact is made with any live electrical part. The 
discharge opening must not be blocked or reduced in size under 
any circumstances. excessive length, over 30 feet (9.14 m), or 
use of more than four elbows can cause restriction and reduce 
the discharge capacity of the valve.