When ducts are used, they shall be of the same cross sectional 
area  as  the  free  area  of  the  openings  to  which  they  connect. 
The minimum dimension of rectangular air ducts shall be not less 
than 3 inches.
air from other indoor spaces
figure 18
The  confined  space  shall  be  provided  with  two  permanent 
openings, one commencing within 12 inches (300 mm) of the top 
and one commencing within 12 inches (300 mm) of the bottom of 
the enclosure. See Figure 18.
each  opening  shall  communicate  directly  with  an  additional 
room(s) of sufficient volume so that the combined volume of all 
spaces meets the criteria for an Unconfined Space.
each opening shall have a minimum free area of 1 square inch 
per 1,000 Btu/hr (2200 mm
2
 per kW) of the aggregate input rating 
of all appliances installed in the enclosure. each opening shall 
not be less than 100 square inches (645 cm
2
). 
outdoor air through two Vertical ducts
The  illustrations  shown  in  this  section  of  the  manual  are  a 
reference  for  the  openings  that  provide  fresh  air  into  confined 
spaces only.
do not  refer  to  these  illustrations  for  the  purpose  of  vent 
installation.  See  Venting  Installation  on  page  15  for  complete 
venting installation instructions.
figure 17
The confined space shall be provided with two permanent vertical 
ducts, one commencing within 12 inches (300 mm) of the top and 
one commencing within 12 inches (300 mm) of the bottom of the 
enclosure. The vertical ducts shall communicate directly with the 
outdoors. See Figure 17.
each duct opening shall have a minimum free area of 1 square 
inch per 4,000 Btu/hr (550 mm
2
 per kW) of the aggregate input 
rating of all appliances installed in the enclosure.