American Water Heater (A)BCG3 85T500-8P Benutzerhandbuch

Seite von 52
19
water heater installation
This  water  heater  is  provided  with  a  properly  rated/sized  and 
certified combination temperature - pressure (T&P) relief valve 
by  the  manufacturer.  See  Temperature-Pressure  relief  Valve 
on  pages  13-14  for  information  on  replacement  and  other 
requirements.
Water Damage Hazard
Temperature-Pressure Relief Valve discharge
pipe must terminate at adequate drain.
CAUTION
Install a discharge pipe between the T&P valve discharge opening 
and  a  suitable  floor  drain.  Do  not  connect  discharge  piping 
directly to the drain unless a 6” (15.2 cm) air gap is provided. 
To prevent bodily injury, hazard to life, or property damage, the 
relief  valve  must  be  allowed  to  discharge  water  in  adequate 
quantities should circumstances demand. If the discharge pipe is 
not connected to a drain or other suitable means, the water flow 
may cause property damage.
t&p Valve discharge pipe requirements:
•  Shall not be smaller in size than the outlet pipe size 
of the valve, or have any reducing couplings or other 
restrictions.
•  Shall not be plugged or blocked.
•  Shall not be exposed to freezing temperatures.
•  Shall be of material listed for hot water distribution.
•  Shall be installed so as to allow complete drainage of both 
the Temperature-Pressure relief Valve and the discharge 
pipe.
•  Must terminate a maximum of six inches above a floor 
drain or external to the building. In cold climates, it is 
recommended that the discharge pipe be terminated at an 
adequate drain inside the building.
•  Shall not have any valve or other obstruction between the 
relief valve and the drain.
The  type,  size  and  location  of  the  relief  valves  must  be  in 
accordance with local codes. The locations of the relief valves 
shown in the installation diagrams are typical. See pages 34-48.  
The heater has a factory installed high temperature limit switch 
and temperature and pressure relief valve.
Cold  water  lines  to  heater  should  be  installed  as  shown  in 
order  to  minimize  gravity  circulation  of  hot  water  to  building 
cold water lines.
A listed temperature and pressure relief valve of adequate capacity 
is installed on the heater.  The locations shown in the installation 
diagrams on pages 34-48 are typical.
The  discharge  opening  of  the  temperature  and  pressure  relief 
valve must be piped to an open drain and should not be subject 
to freezing temperatures.
Install in accordance with all local codes.
water line connections
This manual provides detailed installation diagrams (see pages 
34-48 of this manual) for typical methods of application for the 
water heater(s).
water (potaBle) heating and space heating
1.    All  piping  components  connected  to  this  unit  for  space 
heating applications shall be suitable for use with potable 
water.
2.    Toxic chemicals, such as those used for boiler treatment, 
shall NeVer be introduced into this system.
3.    This  unit  may  NeVer  be  connected  to  any  existing 
heating system or component(s) previously used with a 
non-potable water heating appliance.
4.    When  the  system  requires  water  for  space  heating  at 
temperatures  higher  than  required  for  domestic  water 
purposes, a tempering valve must be installed.  Please 
refer to installation diagrams on pages 34-48 of this manual 
for suggested piping arrangements.
thermometers (not supplied)
Thermometers should be obtained and field installed as shown in 
the installation diagrams.
Thermometers are installed in the system as a means of detecting 
the temperature of the outlet water supply.
water piping diagrams
This manual provides detailed water piping diagrams for typical 
methods of application for the water heaters, see Water Piping 
Diagrams beginning on page 34.
The water heater may be installed by itself, or with a separate 
storage tank, on both single and two-temperature systems.  When 
used with a separate storage tank, the circulation may be either 
by gravity or by means of a circulating pump.  When a circulating 
pump is used it is important to note that the flow rate should be 
slow so that there will be a minimum of turbulence inside the heater.
Adjust  flow  by  throttling  a  full  port  ball  valve  installed  in  the 
circulating line on the outlet side of the pump. Never throttle flow 
on the suction side of a pump.
t&p ValVe discharge pipe
Explosion Hazard
Temperature-Pressure Relief Valve
must comply with ANSI Z21.22-
CSA 4.4 and ASME code.
Properly sized temperature-
pressure relief valve must be
installed in opening provided.
Can result in overheating and
excessive tank pressure.
Can cause serious injury or death.