When checking the Temperature-Pressure relief Valve operation, 
make sure that (1) no one is in front of or around the outlet of the 
Temperature-Pressure relief Valve discharge line, and (2) that 
the water discharge will not cause any property damage, as the 
water may be extremely hot. Use care when operating valve as 
the valve may be hot.
To  check  the  relief  valve,  lift  the  lever  at  the  end  of  the  valve 
several times, see Figure 26. The valve should seat properly and 
operate freely.
If after manually operating the valve, it fails to completely reset 
and continues to release water, immediately close the cold water 
inlet to the water heater and drain the water heater according to 
the Draining and Flushing instructions on page 27. replace the 
Temperature-Pressure relief Valve with a properly rated/sized new 
one, see Temperature-Pressure relief Valve on pages 13-14 for 
instructions on replacement.
figure 26
If  the Temperature-Pressure  relief  Valve  on  the  water  heater 
weeps  or  discharges  periodically,  this  may  be  due  to  thermal 
expansion.
NOTe: excessive water pressure is the most common cause of 
Temperature-Pressure  relief  Valve  leakage.  excessive  water 
system pressure is most often caused by "thermal expansion" 
in a "closed system." See Closed Water Systems and Thermal 
checking the input
For appliance installation locations with elevations above 2000 
feet, refer to hIGh ALTITUDe INSTALLATIONS section of this 
manual for input reduction procedure.
1.  Attach  a  pressure  gauge  or  a  manometer  to  the  manifold 
pressure tap on the gas valve and  refer to Table 3, page 8 for 
correct manifold pressure.
2.  Use this formula to “clock” the meter.  Be sure that other gas  
consuming appliances are not operating during this interval.
  (3600/T) x h = Btuh
  T  =  Time in seconds to burn one cubic foot of gas.
  h = Btu’s per cubic foot of gas.
  Btuh = Actual heater input.
  example: (Using BCG385T500-8N heater)
  T = 7.56 seconds
  h = 1050 Btu
  Btuh = ?
  (3600/7.56)  X  1050  =  500,000  Btuh  (Compare  with  the 
BCG385T500-8N model and rating.)
Should it be necessary to adjust the gas pressure to the burners 
to obtain the full input rate, the steps below should be followed:
3.  remove the regulator adjustment sealing cap, fig. 25, and adjust 
the pressure by turning the adjusting screw with a screwdriver.
 
 Clockwise to increase gas pressure and input rate.
 
 Counterclockwise to decrease gas pressure and input rate.
4. “Clock” the meter as in step 2 above.
5. repeat steps 3 and 4 until the specified input rate is achieved.
6. Turn  the  gas  control  knob  to  PILOT.  remove  the  pressure 
gauge and replace the sealing cap and the threaded plug in 
the pressure tap opening.
UNDer  NO  CIrCUMSTANCeS  ShOULD  The  GAS  INPUT 
eXCeeD The INPUT ShOWN ON The heATer MODeL AND 
rATING PLATe. OVerFIrING COULD reSULT IN DAMAGe 
Or SOOTING OF The heATer.
Venting system
examine the venting system every six months for obstructions 
and/or deterioration of the vent piping.
remove all soot or other obstructions from chimney which will 
retard free draft.
remote storage tank temperature control
The  water  temperature  in  the  remote  storage  tank  (if  used)  is 
controlled by the storage tank temperature control.  The sensing 
element  is  mounted  in  the  hot  water  storage  tank,  see  Water 
Piping Diagram section.
A change in water temperature in the storage tank lower than 
the  tank  temperature  control  setting  will  cause  the  sensor  to 
activate the circulating pump.  The pump then circulates the water 
through the heater where the thermostat senses the drop in water 
temperature and activates main burner operation of the appliance.
If the storage tank temperature control is out of calibration, replace 
with new control.
ShOULD OVerheATING OCCUr Or The GAS SUPPLy FAIL 
TO ShUT OFF, TUrN OFF The MANUAL GAS CONTrOL VALVe 
TO The APPLIANCe. 
temperature-pressure relief ValVe test
It is recommended that the Temperature-Pressure relief Valve 
should be checked to ensure that it is in operating condition every 
6 months.
maintenance