DRAIN VALVE AND ACCESS PANELS
The heaters are equipped with a 3/4" drain valve.
An access panel covers the cleanout opening in the tank which is sealed by 
a gasket and cover, figure 25.
RELIEF VALVE
At least twice a year, the temperature and pressure relief valve should be 
checked to ensure that it is in operating condition.  To check the relief valve, 
lift the lever at the end of the valve several times.  The valve should seat 
properly and operate freely.
If water does not flow, remove and inspect for obstructions or corrosion. 
Replace with a new valve of the recommended size as necessary. Inspection 
of the valve should be performed at least every three years. Do not attempt 
to repair the valve, as this could result in improper operation and a tank 
explosion. In areas with poor water conditions, it may be necessary to inspect 
the T&P valve more often than every three  years.
 CAUTION
BEFORE  MANUALLY  OPERATING THE  VALVE,  MAKE  SURE THAT A 
DRAIN  LINE  HAS  BEEN ATTACHED TO THE  VALVE TO  DIRECT THE 
DISCHARGE TO AN OPEN DRAIN.  FAILURE TO TAKE THIS PRECAUTION 
COULD MEAN CONTACT WITH EXTREMELY HOT WATER PASSING OUT 
THE VALVE DURING THIS CHECKING OPERATION.
I
f  the  temperature  and  pressure  relief  valve  on  the  heater  discharges 
periodically or continuously, it may be due to thermal expansion of water in 
a closed water supply system, or, it may be due to a faulty relief valve.
Thermal expansion is the normal response of water when it is heated.  
In a closed system, thermal expansion will cause the system pressure 
to  build  until  the  relief  valve  actuation  pressure  is  equaled.   Then,  the 
relief  valve  will  open,  allowing  some  water  to  escape,  slightly  lowering 
the pressure.
Contact your water supplier or local plumbing inspector on how to control 
this situation.
Two common corrections are listed in the Checklist and Service Information 
which appears later in this manual.
ABOVE ALL,  DO  NOT  PLUG  THE  TEMPERATURE AND  PRESSURE 
RELIEF  VALVE.  THIS  IS  NOT A  SOLUTION AND  CAN  CREATE A 
HAZARDOUS SITUATION.
CIRCULATING PUMP
The water heating system may include a circulating pump.  Where used, it 
should be lubricated as directed by the circulator manufacturer.
VENT SYSTEM
Examine the vent system every 3 months. Points of inspection are 
as follows:
1.  Check for obstructions and/or deterioration of vent piping and vent hood. 
Replace immediately where needed.
2.  Vent pipe and vent hood screen should be cleaned of foreign material and 
soot. The screen is located inside the vent hood outlet and is accessible 
from the outside of the hood. Do not reach inside the vent hood when 
the heater is in operation.
3.  Check all vent system connections for leakage and reseal as required 
using Hi Temp Silicone sealer or equivalent.