American Water Heater American Water Heaters Residential Gas Water Heater Benutzerhandbuch

Seite von 40
24
vent attenuatIon asseMBlY
InstallatIon  InstructIons
The  Vent Attenuation Assembly  (VAA)  is  designed  to  provide  a
reduction in fan noise created in the blower wheel. This installation 
of this VAA is optional. Review directions thoroughly prior to installing 
the new VAA. Please contact the manufacturer of the water heater as 
shown in the instruction manual with any questions or for additional 
product support.
vent attenuatIon asseMBlY KIt parts lIst
The kit consists of the following items. If a part is missing, use the 
contact information in the instruction manual to acquire missing 
component(s).
• vent attenuation assembly
• flexible tubing
• instruction sheet
vent attenuatIon asseMBlY InstallatIon
The VAA is designed for both vertical and horizontal installations. 
The vertical installation and horizontal installations will require that 
the flexible condensate hose to be attached to the condensate hose
barb located on the bottom of the VAA to release condensate. See 
instructions and diagrams that follow for a more detailed description.
Breathing Hazard - Carbon Monoxide Gas
• 
Do NOT block the holes in the hex plug of vent pipe 
  assembly #1.
• 
Do NOT elevate any portion of the field supplied drain 
  line beyond the 1/2" adaptor above the adaptor. This 
  must be true for entire length of the drain line including 
  the exit into an appropriate drain.
• 
Condensate lines must be free and clear of debris and 
 
must not allow back flow through drain line. Condensate 
 
lines must be able to flow freely to an appropriate drain.
• 
Do not allow condensate lines to become crimped closed.
• 
Analyze entire vent system to make sure that condensate
  will not become trapped in a section of vent pipe and 
  therefore reduce open cross sectional area of vent.
Breathing carbon monoxide can cause brain damage or death.
Always read and understand instruction manual.
Vertical VAA Installations (Recommended)
1.  The VAA is designed to accept two inch PVC pipe into  
the adapters on both ends. The VAA must be installed with the 
condensate hose barb pointing downward. See Figure 22. The 
VAA has an embossed flow arrow to reflect proper orientation.
For optimum performance, install VAA as close as possible to  
the blower assembly.
2.  Use standard PVC cement (not included with kit) and glue the two
inch PVC pipe coming from the blower into the VAA.
3.  Perform the same sequence on the PVC pipe coming from the 
exhaust side (vent terminal side) of the VAA.
4.  Make sure the VAA and vent pipe is supported securely to 
a  permanent  fixture  (stud  or  wall).  Use  standard  support
straps  (not  supplied  with  kit)  that  may  be  found  at  a  local
hardware store. Failure to properly support the VAA and the 
surrounding vent pipe could create a hazardous situation. DO 
NOT puncture any surface of the VAA.
5.  Locate flexible tubing. Slide one end of tubing over the hose 
barb located near end of the VAA. The ridges on the hose 
barb should prevent the tubing from sliding off, however, 
to ensure there are no leaks and possible dislocation from 
hose barb, use a wire tie or hose clamp (not supplied with kit)  
and secure.
6.  Take the other end of the flexible  tubing and slide it through 
the hose clamp on the jacket top cover and install it into one 
of the four barb fittings in vent pipe assembly #2.
7.  Once installed along with the rest of the vent configuration, 
make sure to operate the unit through at least one heat up 
cycle to ensure there is no leakage around the hose barb or 
any joints of the VAA or vent pipe system.
fIGure 22: typical vertical Installation
horizontal vaa Installations
1.  The VAA is designed to accept two inch PVC pipe into the 
adapters on both ends. The VAA must be installed with the 
condensate hose barb pointing downward. See Figure 23. The 
VAA has an embossed flow arrow to reflect proper orientation. 
For optimum performance, install VAA as close as possible 
to the blower assembly.
2.  Use standard PVC cement (not included with kit) and glue the
two inch PVC pipe coming from the blower into the VAA.
3.  Perform the same sequence on the PVC pipe coming from the 
exhaust side (vent terminal side) of the VAA.
4.  Make sure the VAA and vent pipe is supported securely to a 
permanent fixture (stud or wall). Use standard support straps
(not supplied with kit) that may be found at a local hardware
store. Failure to properly support the VAA and the surrounding 
vent pipe could create a hazardous situation. DO NOT puncture 
any surface of theVAA.
5.  Locate flexible tubing. Slide one end of tube over the hose 
barb located near end of the VAA. The ridges on the hose 
barb should prevent the tube from sliding off, however, to 
ensure there are no leaks and possible dislocation from hose