IMMERSION WELLS AND COMPRESSION FITTINGS
7
68-0040—04
GENERAL INFORMATION
Immersion Wells
An immersion well consists of a metal tube, called the well 
shell, closed on one end. A well spud externally threaded to fit 
standard boiler tappings is welded or brazed on the open end. 
See Fig. 1. The well is inserted into the tank and the 
temperature sensing bulb is inserted into the well. The sensing 
bulb never touches the controlled medium. Because the well 
conducts heat rapidly, the bulb responds quickly and 
accurately to temperature changes in the controlled medium.
An immersion well protects the temperature sensing bulb from 
mechanical damage or damage due to chemical interaction 
with the controlled medium. Also, a well permits removal of the 
sensing bulb for testing or control replacement without draining 
the system. The threaded fitting of the well spud provides a 
tighter seal than a packing nut applied to the capillary.
Material Selection
The immersion well material must conduct heat readily and 
resist corrosive and electrolytic action (especially in brine 
solutions and when the well is a different material than the 
container). The material must also resist fluid contamination 
from chemical reaction with the well and withstand high 
temperatures. Most Honeywell immersion wells are copper 
because of its high conductivity. Stainless steel, mild steel and 
Monel wells are also available for applications requiring higher 
maximum temperature and pressure ratings or greater 
corrosion resistance. Some copper wells are available with a 
plastic sleeve over the tube to reduce electrolytic and corrosive 
activity.
Well Sizing
Major factors in selecting well size are:
size of the boiler tapping.
bulb diameter.
insulation depth.
insertion length.
Immersion wells are available to fit standard 1/2-14 NPT and 3/
4-14 NPT tappings. Sensing bulbs are 3/8, 1/2 or 11/16 in. in 
diameter with well shells designed to fit these diameters. The 
bulb should fit tightly in the shell. If the bulb fits loosely, fill the 
space between the shell and bulb with heat-conductive 
compound to ensure maximum heat transfer. Many Honeywell 
temperature controllers ship with heat-conductive compound; 
available in 4-oz cans and 1/2-oz single-application tubes. See 
Table 4.
he nominal length of the spud, including the full length of the 
threads and the hex, defines the insulation depth. Depending 
on the characteristics of the tapping, 1/8 to 1/2 in. of the 
Table 6. Accessories for Duct-Mount Applications
Description
Application
Size
Part Number
Bulb shield assembly
Shields bulb from weather; 
less mounting screws and 
split plug.
6 in. (152 mm) long; holds 3/8 
in. and 1/2 bulbs.
Shields bulb from weather; 
includes mounting screws 
and 33578 Split Plug.
7 in. (118 mm) long, clip holds 
3/8 in. bulb.
Pipe Strap
Fastens bulb to outside of 
pipe.
4-1/2 in. (114 mm) long; used 
with up to 3/4 in. OD pipe.
M17284
107323A
M17285
34886A
M17286
105900