9.4 Troubleshooting in bus connection
9.4.1 Locating error positions
9 - 13
9
E
RROR CODES
 AND 
E
RROR ME
SSAGES
APPE
NDICES
INDEX
Error 
Code
Error
 Messages
Check Timing
Cause and check point
Error detail
Remedy
Correspond-
ing CPU
2110
SP. UNIT 
ERROR.
When instruction 
executed
The FROM/TO instruction is executed to 
any module other than the special func-
tion module.
(1)  Review the sequence program.
(2)  Replace the faulty module with a 
new one.
QCPU
QnACPU
2111
The location designated by link direct 
device (J
/
) is not a network module.
2112
When instruction 
executed/
STOP
RUN
(1)  The location designated by a 
special function module dedicated 
instruction is not a special function 
module.
(2)  Alternatively, it is not the relevant 
special function module.
Review the sequence program.
2113
No special function module data for simu-
lation purposes has been set in the simu-
lation data.
Read error individual information, then 
check and edit the special function mod-
ule simulation data that corresponds to 
the numerical value there (program 
error location).
2120
SP. UNIT 
LAY ERR.
At CPU power ON/
At reset
The location of Q
B and QA1S
B is 
improper.
Check the location of the base unit.
QCPU
2122
QA1S
B is installed to the basic base 
unit.
Install Q
B as the basic base unit.
2124
(1) A module is installed at 65th or later 
slot.
(2) A module is installed at the slot later 
than the number of slots specified 
with base allocation setting.
(3) A module is installed at the I/O 
points later than the 4,096th point.
(4) A module installed at the 4,096th 
point occupies later points.
(1)  Remove the module installed at 
65th or later slot.
(2)  Remove the module installed at 
the slot later than the number of 
slots specified with base 
allocation setting.
(3)  Remove the module installed at 
the I/O points later than the 
4,096th point.
(4)  Change the last module to a 
module which does not exceed 
the 4,096th point.
2125
(1) A module which the QCPU cannot 
recognize has been installed.
(2) There was no response form the 
intelligent function module.
(1)  Install a module which can be 
used with the QCPU.
(2)  Replace the faulty module with a 
new one.
5000
WDT 
ERROR.
Always
Program scan time for initial execution 
type program goes over the initial execu-
tion WDT time set in the parameter PC 
RAS settings.
Read the error individual information at 
a peripheral device, check the numerical 
value (time) there, and shorten scan 
time if necessary.
QCPU
QnACPU
5001
Program scan time goes over the WDT 
value set in the parameter PC RAS set-
tings.