SPECIFICATIONS
STANDBY EMERGENCY GENERATOR
Type......................................................................Synchronous
Rotor Insulation .............................................................Class H
Stator Insulation ............................................................Class H
Alternator Output Leads 3-phase ..................................... 4-wire
Bearings ..................................................................Sealed Ball
Coupling ................................................................Flexible Disc
Load Capacity (Standby Rating) ...............................25/30 kW*
*  NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE 
J1349, ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate 
with natural gas.
Excitation System ............................................................Direct
Generator Output Voltage/kW - 60 Hz
 kW 
Amp 
CB 
Size
 120/240V, 1-phase, 1.0 pf  25/30 
104/125 
125/150
 120/208V, 3-phase, 0.8 pf  25/30 
87/104 
100/125
 120/240V, 3-phase, 0.8 pf  25/30 
75/90 
90/100
Generator Locked Rotor KVA Available @ Voltage Dip of 35%
 25kW 
30kW
 
35 KVA 
45 KVA
ENGINE
Make ........................................................................... Generac
Model .............................................................................In Line
Cylinders and Arrangement .....................................................4
Displacement ............................................................... 1.6  Liter
Bore..............................................................................3.15 in.
Stroke ...........................................................................3.13  in.
Compression Ratio....................................................... 9.5-to-1
Air Intake System ......................................... Naturally Aspirated
Valve Seats ............................................................ Replaceable
Lifter Type .................................................................. Hydraulic
Spark Plug Gap ........................................0.76mm (0.030 inch)
Engine Parameters
Rated Synchronous RPM .......................................60 Hz, 3600
Exhaust System
Exhaust Flow at Rated Output 60 Hz:  25kW 
30kW
 
240 cfm 
260 cfm
Exhaust Temp. at Rated Output: 
975°F 
1025°F
Combustion Air Requirements (Natural Gas)
Flow at rated power, 60 Hz: 
25kW 
30kW
 
90 cfm 
95 cfm
Governor
Type...........................................................................Electronic
Frequency Regulation .............................................Isochronous
Steady State Regulation ................................................± .25%
Adjustments:
  Speed ..................................................................... Selectable
Engine Lubrication System
Type of Oil Pump ...............................................................Gear
Oil Filter .......................................................Full Flow, Cartridge
Crankcase Oil Capacity ............................................ 4 U.S. qts.
COOLING SYSTEM
Type............................................................................... Closed
Water Pump ............................................................. Belt Driven
Fan Speed .........................................................................2484
Fan Diameter ...........................................................17.7 inches
Fan Mode ....................................................................... Pusher
Air Flow (inlet air including alternator and
  combustion air) ..................................................1800 ft
3
/min.
Coolant Capacity ....................................................2.0 U.S. gal.
Heat Rejection to Coolant (25/35kW) ....112,000/135,000 Btu/h
Maximum Operating Air Temp. on Radiator ......... 60° C (150° F)
Maximum Ambient Temperature ......................... 50° C (140° F)
FUEL SYSTEM
Type of Fuel ....................................Natural Gas, Propane Vapor
Carburetor............................................................... Down Draft
Secondary Fuel Regulator............................................ Standard
Fuel Shut-off Solenoid ................................................. Standard
Operating Fuel Pressure  ................. 5 in. - 14 in. Water Column
Fuel Consumption - ft
3
/hr (Natural Gas/LPV)
 
Exercise 25% 50% 75% 100%
 
Cycle  Load Load Load Load
25kW 60/24 120/48 
220/87 
310/123 
390/155
30kW 60/24 145/58 
260/103 
370/147 
470/187
ELECTRICAL SYSTEM
Battery Charge Alternator ......................................12V, 15 Amp
Static Battery Charger ....................................... 2.0 or 2.5 Amp
Recommended Battery .................................Group 26, 525CCA
System Voltage ............................................................ 12 Volts
Voltage Regulator
Type...........................................................................Electronic
Sensing ................................................................ Single-phase
Regulation ........................................................................±  1%
Features .........................Adjustable Voltage and Automatic Gain
Power Adjustment for Ambient Conditions
Temperature Deration:
  3% for every 10° C above °C 
25kW 
30kW
 40 
25
  1.65% for every 10° above °F 
104 
77
Altitude Deration:
  1% for every 100 m above m 
25kW 
30kW
 915 
182
  3% for every 1000 ft. above ft. 
2000 
600
Controller ................................................................. Nexus
6-1
GenSpec082  Rev
. C  12/11
Specifications