dca220sscu/4i 60 hz generaTor• operaTion manual — rev. #0 (10/25/12) — page 25
GeNeratOr OUtpUts/GaUGe reaDiNG
hoW To  read The  ac  ammeTer  and  ac 
volTage gauges
The AC ammeter and AC voltmeter gauges are controlled 
by the AC ammeter and AC voltmeter change-over switches.
Both of these switches are located on the control panel and 
do noT effect the generator output. They are provided to 
help observe how much power is being supplied, produced 
at the UVWO terminals lugs.
Before taking a reading from either gauge, configure the 
Voltage Change-Over Board (Figure 13) which produces 
the desired output voltage. 
Figure 13. Voltage Change-Over Board 
240/3
Ø Position
ac voltmeter gauge reading
Place the
 AC Voltmeter Change-Over Switch (Figure 14) 
in the W-U position and observe the phase to phase voltage 
reading between the W and U terminals as indicated on 
the 
AC Voltmeter Gauge (Figure 15).
Figure 14. AC Voltmeter 
Change-Over Switch
Figure 15. AC Voltmeter Gauge 
(Volt reading on W-U Lug)
ac ammeter gauge reading
Place the
 AC Ammeter Change-Over Switch (Figure 16) 
in the U position and observe the current reading (load 
drain) on the U terminal as indicated on the 
AC Ammeter 
Gauge  (Figure  17). This  process  can  be  repeated  for 
terminals V and W.
Figure 16. AC Ammeter 
Change-Over Switch
Figure 17. AC Ammeter 
(Amp reading on U Lug)
NOTICE
The 
ammeter gauge will only show a reading when 
the 
Output Terminal Lugs are connected to a load 
and in use.