Multiquip DCA220SSCU4i Benutzerhandbuch

Seite von 90
page 28 — dca220sscu/4i 60 hz generaTor • operaTion and parTs manual — rev. #0 (10/25/12) 
iNspeCtiON/setUp
circuiT BreaKers
To protect the generator from an overload, a 3-pole, 600 
amp, main circuit breaker is provided to protect the 
u,v, 
and W output Terminals from overload. In addition two 
single-pole, 20 amp 
gFci circuit breakers are provided to 
protect the GFCI receptacles from overload. Three 50 amp 
load circuit breakers have also been provided to protect the 
auxiliary receptacles from overload. Make sure to switch 
all circuit breakers to the oFF position prior to starting 
the engine.
luBricaTion oil
Fill the engine crankcase with lubricating oil through the 
filler hole, but 
do noT overfill. Make sure the generator is 
level and verify that the oil level is maintained between the 
two notches (Figure 27) on the dipstick. See Table 9 for 
proper selection of engine oil.
Figure 27. Engine Oil Dipstick
When checking the engine oil, be sure to check if the oil is 
clean. If the oil is not clean, drain the oil by removing the 
oil drain plug, and refill with the specified amount of oil as 
outlined in the 
cummins engine owner’s manual. Oil 
should be warm before draining.
Delo® engine oil is the recommended engine oil for this 
generator. When replacing engine oil please refill using 
Delo® 400 LE SAE 15W-40 (API CJ-4) engine oil.
Table 9. recommended motor oil
Fuel checK
refilling the Fuel system 
This  generator  has  an  internal  fuel  tank  located  inside 
the  trailer  frame  and  may  also  be  equipped  with  an 
environmental fuel tank (Figure 28). 
alWaYs fill the fuel 
tanks with clean fresh 
#2 diesel fuel. do noT fill the fuel 
tanks beyond their capacities.
Pay attention to the fuel tank capacity when replenishing 
fuel. The fuel tank cap must be closed tightly after filling. 
Handle fuel in a safety container. If the container does not 
have  a  spout,  use  a  funnel. Wipe  up  any  spilled  fuel 
immediately.
Figure 28. Internal Fuel Tank System
  danger
Fuel spillage on a 
hot engine can cause 
fire or explosion. If fuel spillage occurs, 
wipe  up  the  spilled  fuel  completely  to 
prevent  fire  hazards. 
never  smoke 
around or near the generator.
  cauTion
onlY  properly  trained  personnel  who  have  read 
and understand this section should refill the fuel tank 
system.
Generator Internal Fuel Tank
Trailer Fuel Tank