  Maintenance  Level 1 
 
Level 2 
 
Level 3 
 
Level 4 
 
Level5
 Tasks
 
Recom-
 
Task Required Task Required Task 
 
Task Required Task
 
 
mended 
Comp.  to be done  Comp.  to be done  Comp. 
Required 
Comp.  to be done  Comp.
 
 
to be done  (Date-  3 months/  (Date- 
Semi- 
(Date-  to be done  (Date- 
Bi- 
(Date-
 
 
monthly/ Initials) Break-in Initials) annually/ Initials) Annually/ Initials) annually/ Initials)
 
 
10 hrs. 
 
30 hrs. 
 
50 hrs. 
 
100 hrs. 
 
250 hrs.
18.  Start and
exercise the unit
at full rated load
(use a load bank
if the site load is
not enough) for
at least 2 hours
looking for leaks,
loose
connections or
components, and
abnormal
operating
conditions.
Correct as
necessary.
19.  Perform an
engine oil
analysis (send a
sample to a lab
for results).
Change the
engine oil and
filters if the
analysis results
indicate this is
required.
20.  Change the
engine oil.
21.  Replace the
engine oil filter(s).
22.  Replace engine
spark plugs.
Clean and re-gap
or replace as
necessary.
23.  Replace the
engine air
filter(s).
24.  Perform a 5
minute no-load
operational run
of the unit
looking for any
post service
problems.
25.  Return the unit
to standby setup
for operation
when required.
11-4
Standby Generator Sets
Service Schedule
SrvSchd001  Re
v. A  09/05