Siemens 580 Benutzerhandbuch

Seite von 35
- 10 - 
Installation 
 
 
Typical Motor Control Settings 
 
 
Alarm 
Trip 
(Shutdown) 
Timer Trip 
Setting 
(1)
 
Winding Temperature 
  Class B Insulation 
  Class F Insulation 
 
130°C 
155°C 
 
155°C 
170°C 
 
 
Motor Bearing Temperature 
(Thermocouple or RTD’s) 
 
 
 
 Sleeve 
Bearing 
100°C 105°C 
 
 Antifriction 
Bearing 
100°C 105°C 
 
 
 
 
 
Ground Fault 
4 Amps 
(2)
 
Primary 
Circuit 
8 Amps 
(2)
 
Primary 
Circuit 
0.2 sec. 
(2)
 
Instantaneous Overcurrent 
 
 
  With ½ Cycle Delay 
1.8 times Locked Rotor Amps 
(2)
 
 
  Without Time Delay 
2.4 times Locked Rotor Amps 
(2)
 
 
 
 
 
Maximum Voltage 
110 % of Rated Voltage 
10 sec. 
Minimum Voltage 
(the minimum voltage 
also applies to starting unless otherwise 
specified) 
90 % of Rated Voltage 
10 sec. 
Maximum Frequency Deviation 
±5% 
10 sec. 
Maximum of Voltage Plus Frequency Deviation 
±10% 
10 sec. 
Maximum Voltage Unbalance 
(3)
 1% 
15 
sec. 
Maximum Current Unbalance 
(3)
 8% 
15 
sec. 
 
Suggested Vibration Limits
 
RPM 3600 
1800 1200 
900 
and 
Slower 
Shaft (mils, pk-to-pk) 
3.3 
3.7 
4.3 
5.0 
Housing (in./sec.) 
0.25 
0.25 
0.25 
0.25 
 
(1)
 Maximum time at maximum condition before control device is to operate. 
(2)
 Increase as necessary to avoid nuisance trips. 
(3)
 This is the maximum deviation from the average of the three phases.