Ethernet Connections
Chapter 5 - Features and Applications 
Page 111
Meter Setup for Ethernet Communications 
To enable communications through the meter’s Ethernet port, you must configure 
the Ethernet communications module. The IP AddressSubnet Mask, Gateway, 
SMTP Server
 and SMTP Connection Timeout setup registers must properly match 
your system and can be set through the meter’s front panel, or with Designer 
software. 
Configuring the Ethernet Module through the Front Panel
1.
From the S
ELECT
 S
ETUP
 menu, choose Q
UICK
 S
ETUP
 > E
THERNET
.
2.
Configure the E
THERNET
 communications module IP AddressSubnet Mask, 
Gateway, SMTP Server and SMTP Connection Timeout setup registers to match 
your communications system. 
Configuring the Ethernet Module via Designer
After you have wired your meter to the Ethernet network and performed basic 
setup, add the meter to your WinPM.Net network using the Management Console. 
(It is not necessary/possible to add an Ethernet site.)
Adding an Ethernet Device to your WinPM.Net Network
In the Management Console, the Ethernet Device Options screen appears when you 
add an Ethernet device (meter). Use this screen to describe your meter Ethernet 
address and other communications information. Be sure to include:
The server computer that will communicate with the Ethernet device.
The Ethernet device TCP/IP address.
Configuring the Ethernet Communications Module in Designer
To enable communications through the Ethernet port, you must configure the 
Ethernet communications module. Launch Designer and configure the IP Address
Subnet Mask, Gateway, SMTP Server and SMTP Connection Timeout registers to 
match your system.
Server computer that 
communicates with the 
Ethernet device
Meter TCP/IP Address