Siemens 9300 Benutzerhandbuch

Seite von 176
9300 Series User’s Guide
Internal Modem Connections
Chapter 5 - Features and Applications 
Page 115
Configuring the Comm 1 Communications Module in Designer
Launch Designer, and configure the Comm 1 communications module Baud Rate, 
Unit ID, and Protocol setup registers to match your communications system. 
Configure the initialization string for the internal modem using the ModemInit 
register. Refer to “ModemInit Setup Register” on page 113.
The ModemGate Protocol
The ModemGate feature creates a communications connection between the 
telephone network and an RS-485 serial network of devices (loop or straight-line 
topology). When you specify the protocol for the meter’s COM 1 port as 
MODEMGATE
, all data received by the meter’s internal modem is automatically 
transferred to the serial network.
ModemGate is only available for the 9330 and 9350 meters, and it is only 
configurable on the COM 1 port. 
Server computer that 
communicates with the 
remote modem. Ensure that 
the server computer dialout 
modem is configured. 
Remote modem telephone 
number
Telephone
Network
Meter with an 
internal modem.
The serial network 
is connected to 
COM 1.
Workstation with 
WinPM.Net and 
modem
Each device on the RS-485 loop, 
including the gateway meter’s internal 
modem, must have a unique Unit ID 
number.
All serial devices must operate at the 
same baud rate as the gateway meter.