Aprilaire 8051 Merkblatt

Seite von 2
P.O. Box 1467 • Madison, WI 53701-1467 • Phone: 800/334-6011 • Fax: 608/257-4357 •
www.aprilairepartners.com
61000944   3.12
B2205800A
© 2012 Aprilaire – A division of Research Products Corporation
aprIlaIre
®
 Model 8051 FluSh Mount SenSor InStallatIon InStructIonS
Step 1:   Use a 1” paddle bit to drill a 1” dia. hole in the drywall/sheetrock. Keep the drill steady and horizontal to ensure a clean finished hole.
Step 2:   Wire nut the sensor to cable run between the flush mount sensor and the thermostat or support module. Press the sensor into the 1” hole
after the wires are connected.
 
IMportant: Do not spackle or mud over the sensor. The sensor must protrude 1/64” from the wall for accurate temperature reporting.
Step 3:   Wire the sensor to the thermostat or support module. Refer to the instructions provided with these devices for additional details.
1”
1.00”
THERMOSTAT 
OR 
SUPPORT MODULE
note: Paint or apply wall paper to the sensor 
disk prior to installing the sensor into the wall.
PRESS FLUSH MOUNT TEMPERATURE SENSOR
INTO 1” HOLE. NO FASTENERS REQUIRED.
61000944A AA 8051 Flush Mount Sensor Install.indd   2
3/28/12   11:38 AM