Toshiba TOSVERT VF-AS1 Gebrauchsanleitung

Seite von 73
E6581315
36
„
  Relating communication parameters
Following parameters should be set or changed if necessary.
• Baud rate (, )... Shipment setting = : 19200bps
    Baud rate of all inverters in the network (master and slave) should be same network.
• Parity () ... Shipment setting = : Even parity
Parity of all inverters in the network (master and slave) should be same network.
• Communication time-out time() ... Shipment setting = 
Operation is continued by the last received command value in the case of a communication break-
down. To stop the operation of inverter, provide a communication time-out time (ex. =
 sec-
ond
) to the slave inverters. The master inverter does not trip even though the communication break-
down happens. To trip the master inverter, provide an interlock mechanism by installing a FL fault
relay point or the like from the slave side.
• Frequency point selection (, )
Adjusted to the system.
See chapter “6.1 Speed proportional control” for details.
„
  Setting example of parameters (2-wire RS485 communication)
Parameters relating to the master side (example)

     Master (transmission of output frequency
                       (%) (100% at FH))

      Selection of communication protocol
               (Toshiba inverter protocol)

      Communication baud rate
(ex. 19200bps)

            Parity (even parity)

      Example: Panel

  Example: RR/S4 input
<During torque control>

   
Master (sends a torque command)
Parameters relating to the slave side (example)

 Slave (If the master inverter trips, all slave inverters stop
operating.)

   Selection of communication protocol
               (Toshiba inverter protocol)

   Communication time-out (ex. 1 second)

      Communication baud rate (same to the master side)

   Parity (same to the master side)

      Terminal block (ex. Driven by F, ST)
( Run and stop of operation is controlled with the frequency
reference value by setting the “run frequency”.)

   Operation panel RS485 (2-wire) communication input

    2-wire RS485

?    Adjusted to the system  Point 1 setting (%)

  ?    Ditto                  Point 2 frequency (Hz)

    ?        Ditto                                    Point 2 setting (%)

  ?    Ditto                  Point 2 frequency (Hz)
<During torque control>

RS485 communication input

Load sharing gain input mode selection (ex. Operation
panel input enabled)

Panel load sharing gain (ex. Sharing of half of the com-
mand value)