Hitachi SJ300-037HFE Benutzerhandbuch

Seite von 289
“C” Group: Intelligent Terminal Functions
Configur
ing Dr
iv
P
a
ra
meters
3–58
C044
PID deviation level 
setting
Sets the PID loop error 
threshold  |SP - PV| 
(absolute value) to trigger 
intelligent output [OD]. 
Range is 0.0 to 100%, 
resolution is 0.1%
✘ ✔
3.0
3.0
3.0
%
>C044 PID
LEVEL     003.0%
C045
Frequency arrival 
setting for acceleration 
(2)
Range is 0.0 to 99.99 / 
100.0 to 400.0 Hz
✘ ✔ 0.00 0.00 0.00
Hz
>C045 ARV
ACC2   0000.00Hz
C046
Frequency arrival 
setting for deceleration 
(2)
Range is 0.0 to 99.99 / 
100.0 to 400.0 Hz
✘ ✔ 0.00 0.00 0.00
Hz
>C046 ARV
DEC2   0000.00Hz
C055
Over-torque (forward-
driving) level setting
Threshold for intelligent 
output terminal [OTQ], 
quadrant I. Range is:
0 to 200%, up to –550xxx;
0 to 180%, –750 to 1500xxx
✘ ✔ 100. 100. 100.
%
>C055 OV-TRQ
FW-V        100%
C056
Over-torque (reverse 
regenerating) level 
setting
Threshold for intelligent 
output terminal [OTQ], 
quadrant II. Range is:
0 to 200%, up to –550xxx;
0 to 180%, –750 to 1500xxx
✘ ✔ 100. 100. 100.
%
>C056 OV-TRQ
RV-R        100%
C057
Over-torque (reverse 
driving) level setting
Threshold for intelligent 
output terminal [OTQ], 
quadrant III. Range is:
0 to 200%, up to –550xxx;
0 to 180%, –750 to 1500xxx
✘ ✔ 100. 100. 100.
%
>C057 OV-TRQ
RV-V        100%
C058
Over-torque (forward 
regenerating) level 
setting
Threshold for intelligent 
output terminal [OTQ], 
quadrant IV. Range is:
0 to 200%, up to –550xxx;
0 to 180%, –750 to 1500xxx
✘ ✔ 100. 100. 100.
%
>C058 OV-TRQ
FW-R        100%
C061
Electronic thermal 
warning level setting
Sets the threshold for intelli-
gent output [THM].
Range is 0 to 100%
✘ ✔
80.
80.
80.
%
>C061 E-THM
WARN        080%
C062
Alarm code output
Allows binary alarm codes 
to be output to intelligent 
terminals.
Three option codes:
00 Disable
01 Enable – 3-bit code
02 Enable –  4-bit code
✘ ✔
00
00
00
>C062 AL-CODE
SELECT      OFF
C063
Zero speed detection 
level
Range is 0.00 to 99.99 / 
100.0 Hz
✘ ✔ 0.00 0.00 0.00
Hz
>C063 ZS
LEVEL   000.00Hz
“C” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)