The Bit Operation method of speed control uses up to seven intelligent inputs to select from up 
to eight speeds. Since the all-switches-OFF combination selects the first speed, you only need 
N-1 switches to select N speeds. With Bit Operation speed control, only one input is normally 
active at a time. If multiple switches are ON, the lower numbered input takes precedence 
(determines the speed). The table and figure below show how the input combinations work.
The following table lists the option codes for assigning [SF1 to [SF7] to the intelligent inputs.
0th
SF1
SF2
SF3
3rd
4th
2nd
5th
1st
7th
6th
Speed
Switches
Fwd Run
SF4
SF5
SF6
SF7
Multi-
speed
Input Function
SF7
SF6
SF5
SF4
SF3
SF2
SF1
Speed  0
0
0
0
0
0
0
0
Speed  1
1
Speed  2
1
0
Speed 3
1
0
0
Speed  4
1
0
0
0
Speed  5
1
0
0
0
0
Speed  6
1
0
0
0
0
0
Speed  7
1
0
0
0
0
0
0
Opt.
Code
Symbol
Function Name
Description
32
SF1
Bit-level speed select 1
Bit-level speed select, Bit 0
33
SF2
Bit-level speed select 2
Bit-level speed select, Bit 1
34
SF3
Bit-level speed select 3
Bit-level speed select, Bit 2
35
SF4
Bit-level speed select 4
Bit-level speed select, Bit 3
36
SF5
Bit-level speed select 5
Bit-level speed select, Bit 4
37
SF6
Bit-level speed select 6
Bit-level speed select, Bit 5
38
SF7
Bit-level speed select 7
Bit-level speed select, Bit 6
Valid for 
inputs:
C001, C002, C003, C004, 
C005, C006, C007, C008
Required 
settings:
F001, A020 to A035
A019=00
Notes: 
• 
When all [SFx] inputs are OFF, the speed is 
set by default to the value in F001.
• When a multi-speed setting more than 
50Hz(60Hz) is to be set, it is necessary to 
program the maximum frequency A004 high 
enough to allow that speed.
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
Example: (Requires input configuration—
see page 
. Jumper position shown is 
for –xFU/-xFR models; for –xFE models, 
see page 
SF1
SF3
SF5
SF7
SF2
SF4
SF6