Two-stage
Acceleration and 
Deceleration
When terminal [2CH] is turned ON, the 
inverter changes the rate of acceleration and 
deceleration from the initial settings (F002 
and F003) to use the second set of accelera-
tion/deceleration values. When the terminal 
is turned OFF, the inverter is returned to the 
original acceleration and deceleration time 
(F002 acceleration time 1, and F003 decel-
eration time 1). Use A092 (acceleration 
time 2) and A093 (deceleration time 2) to 
set the second stage acceleration and decel-
eration times.
In the graph shown above, the [2CH] signal becomes active during acceleration. This causes the 
inverter to switch from using acceleration 1 (F002) to acceleration 2 (A092).
Opt.
Code
Symbol
Function Name
Input 
State
Description
09
2CH
Two-stage Accelera-
tion and Decelera-
tion
ON
Frequency output uses 2nd-stage accelera-
tion and deceleration values
OFF
Frequency output uses the initial accelera-
tion 1 and deceleration 1 values
Valid for inputs:
C001, C002, C003, C004, 
C005, C006, C007, C008
Required 
settings:
A092, A093, A094=0
Notes: 
• 
Function A094 selects the method for second 
stage acceleration. It must be set = 00 to 
select the input terminal method in order for 
the [2CH] terminal assignment to operate.
Output
frequency
[FW, RV]
t
target frequency
initial
second
Input
signals
[2CH]
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
See I/O specs on page 
.
Example: (Default input configuration 
shown—see page 
. Jumper position 
shown is for –xFU/-xFR models; for –xFE 
models, see page 
.)
2CH