Troubleshooting
T
roub
leshooting
and Maintenance
6–4
The motor speed will not reach the 
target frequency (desired speed).
• If using the analog input, is there 
current or voltage at [O] or [OI]?
• Check the wiring.
• Check the potentiometer or 
signal generating device.
• Is the load too heavy?
• Reduce the load.
• Heavy loads activate the 
overload restriction feature 
(reduces output as needed).
• Is the inverter internally limiting the 
output frequency?
• Check max frequency setting 
(A004)
Check frequency upper limit 
setting (A061)
If using analog inputs, check 
their settings (A101– A104) 
or (A111–A114), or (A011–
A014)
The rotation is unstable.
• Is the load fluctuation too great?
• Is the supply voltage unstable?
• Is the problem occurring at a particular 
frequency?
• Increase the motor capacity 
(both inverter and motor).
• Fix power supply problem.
• Change the output frequency 
slightly, or use the jump 
frequency setting to skip the 
problem frequency.
The RPM of the motor does not 
match the inverter output 
frequency setting.
• Is the maximum frequency setting 
A004 correct?
• Does the monitor function D001 
display the expected output frequency?
• Verify the V/F settings match 
motor specifications.
• Make sure all scaling (such as 
A011 to A014) is properly set.
A parameter 
will not 
change after 
an edit 
(reverts to old 
setting).
True for certain 
parameters
• Is the inverter in Run Mode? Some 
parameters cannot be edited during 
Run Mode.
• Put inverter in Stop Mode 
(press the Stop/reset key). Then 
edit the parameter.
True for all 
parameters
• If you’re using the [SFT] intelligent 
input (software lock function)—is the 
[SFT] input ON?
• Change the state of the SFT 
input, and check the B031 
parameter (SFT mode).
Symptom/condition
Probable Cause
Solution