CAUTION: Remarks for using ground fault interrupter breakers in the main 
power supply: Adjustable frequency inverters with CE-filters (RFI-filter) 
and shielded (screened) motor cables have a higher leakage current toward 
Earth GND. Especially at the moment of switching ON this can cause an 
inadvertent trip of ground fault interrupter breakers. Because of the rectifier 
on the input side of the inverter there is the possibility to stall the switch-off 
function through small amounts of DC current. Please observe the follow-
ing: • Use only short time-invariant and pulse current-sensitive ground fault 
interrupter breakers with higher trigger current. • Other components should 
be secured with separate ground fault interrupter breakers. • Ground fault 
interrupter breakers in the power input wiring of an inverter are not an 
absolute protection against electric shock.
.............  
.............  
.............  
.............  