29
Installing the Inverter/Charger
Th
is g
u
id
e for use 
by 
qu
alified 
perso
nnel
 o
n
ly.
Guidelines for Routing the DC Cables
Follow these guidelines to ensure maximum performance.
Do not attempt to use the chassis in place of the battery 
negative connection for grounding. The inverter requires a 
reliable return path directly to the battery.
To reduce the chance of radio frequency interference, keep the 
positive and negative cables close together—ideally, held 
together by straps, loom, or insulated clamps at regular 
intervals.
To ensure maximum performance from the inverter/charger, do 
not route your DC cables through a DC distribution panel, 
battery isolator, or other device that will cause additional 
voltage drops. The exception is the DC fuse and Disconnect or 
the DC circuit breaker which is required at the battery to protect 
the DC wiring.
To help avoid damage caused by reverse polarity battery 
connection, it is a good idea to mark each end of each cable to 
identify it as a positive (red) or negative (black) cable before 
routing the wiring.
ELECTRICAL SHOCK AND FIRE HAZARD
Route the cables away from sharp edges that might damage the 
insulation. Avoid sharp bends in the cable.
Failure to follow these instructions can result in minor or moderate 
injury.
Freedom SW 3K2K 230V InvChg Install Guide.book  Page 29  Friday, June 20, 2014  9:11 AM