Lincoln Electric SVM176-A Benutzerhandbuch

Seite von 55
LN-23P
F-4
F-4
TROUBLESHOOTING AND REPAIR
FEEDING  PROBLEMS
Observe Safety Guidelines detailed in the beginning of this manual.
PROBLEMS
(SYMPTOMS)
POSSIBLE AREAS OF
MISADJUSTMENT(S)
RECOMMENDED
COURSE OF ACTION
If for any reason you do not understand the test procedures or are unable to perform the tests/repairs safely,
contact the Lincoln Electric Service Department for technical troubleshooting assistance before you proceed.
Call 1-888-935-3877.
CAUTION
Major physical or electrical
damage is evident when the
sheet metal covers are removed.
Contact the Lincoln Electric
Service Department at 1-888-
935-3877. 
Motor does not run. No Voltage on
the Voltmeter
Motor  does  not  run.  OCV  is
indicated on the meter.
1. Check for power source output.
2. Remote  Sensing  lead  not
connected to work or broken.
3. Control  Cable  to Adapter  Kit
misconnected or defective.
4. Defective Adapter Kit 
1. OCV must be at least 14 VDC.
NOTE: Code 9085 OCV must be
less than 50vdc (45Volts
on DC600).
2. Circuit Breaker tripped.
3. Defective gun trigger or control
leads.
4. Possible defective Control Board
5. Defective Adapter Kit or Control
cable
6. Defective Motor or gearbox.
1. If OK, continue to Step 2.
2. Check continuity of sense lead
circuit. See 
If  meter  reads  backwards,
polarity  is  wrong.  Reverse
polarity of power source. The
LN23P must run on Electrode
Negative.
3 Check continuity of the control
cable.
4. See the 
1. Adjust  power  source  output
accordingly. If OCV cannot be
adjusted below 50 vdc, Code
9085  machines  must  be
upgraded with a new Control
Board.
2. Reset breaker. If it trips again,
check the wire feed system for
restrictions. Perform the 
3. Check  the  trigger  circuit
continuity.  See  the 
4. Perform the 
5. See the 
6. See