GE 994-0089 Benutzerhandbuch

Seite von 92
GE Energy 
 
48 
 
994-0089–1.00–2, General
 
 
4.3 RS-232 
Connections 
The D400 accepts connections to RS-232 type devices through the RS-232 Adapter. The 
RS-232 Adapter (GE Part No. 520-0207) is a standard RS-232 serial I/O adapter card that 
plugs into any serial communication slot (slots 1 through 8) on the D400. It contains two 
independently isolated RS-232 serial ports (Port 1 and Port 2) each with a DB-9 
connector.  
The required RS-232 cable is a serial null modem, DB-9F to DB-9M cable. The cables must 
be shielded and DB-9 connector covers must provide EMC shielding (e.g. metalized plastic 
or die-cast metal covers). 
See section “3.3 RS-232 Adapter” for configuration options. 
» 
To connect RS-232 type devices to the RS-232 Adapter, use the following cable 
connection: 
Relay
1
5
6
9
1
5
6
9
2
3
5
7
8
7
8
2
3
5
 
 
RS-232 Port DB-9 Connector Signal Definitions 
DTE (default) 
DCE  
Pin 
Number 
Function 
Signal Flow 
Function 
Signal Flow 
1 DCD 
IN 
DCD 
IN 
2 RXD 
IN 
TXD 
OUT 
3 TXD 
OUT  RXD 
IN 
4 DTR 
OUT  DSR 
IN 
Signal GND 
Signal GND 
6 DSR 
IN 
DTR 
OUT 
7 RTS 
OUT  CTS 
IN 
8 CTS 
IN 
RTS 
OUT 
Not connected 
Not connected