994-0089–1.00–2, General
 
 
Redundant Power Supply 
The D400 may be provided with an optional redundant power supply unit in Power 
Supply Slot 2. The second power supply provides continuous power to the D400 in the 
event the primary power supply unit fails.  
Additional protection can be provided if a secondary external power source is available. 
In the event the primary power source fails, an automatic switchover will take place to 
the redundant power source to ensure continuous power to the D400. 
Power Configurations 
The D400 supports the following power configurations: 
•  Single External AC Power Source 
•  Single External DC Power Source 
•  Two External AC Power Sources with optional redundant D400 AC-DC Power Supplies 
•  Two External DC Power Sources with optional redundant D400 DC-DC Power 
Converters 
Power Input Ranges 
AC-DC Power Supply 
Rated voltage range 
100-240 VAC / 100-300 VDC with overvoltage protection of 
110 % to 150 % 
If the unit is…  
Then the rated power is… 
AC 
127 VA maximum 
Rated power 
DC  
135 W maximum 
AC-DC 26.5 
A
peak 
(< 145 VAC/205 VDC) 
Inrush current at 25 °C on 
cold start 
AC-DC 40 
A
peak
 (< 264 VAC/370 VDC) 
Rated frequency 
47 to 63 Hz (50/60 Hz) 
 
DC-DC Power Supply 
Rated voltage range 
20-55 VDC with overvoltage protection of 110 % to 150 % 
Rated power 
DC 
135 W maximum 
Inrush current at 25 °C 
DC-DC 35 
A
peak