The D400 includes connections for two power supply alarms: 
•  Power Fail to indicate one of the two power supplies or one of the two power feeds 
has failed 
•  System Fail to indicate system operation status 
Terminal block TB2 on the rear panel of the D400 provides contact closure outputs for 
connection to an external circuit, for example, to connect an external LED indicator or 
audible alarm. 
The contact closure used for alarm outputs is a solid-state photo-MOS device. Contact 
closure output ratings at maximum ambient temperature are: 
•  Continuous current: 0.1 A continuous at 300 VAC / 300 VDC 
•  Peak current: 0.28 A peak for 10 ms 
•  Maximum on resistance: 35 ohm 
Power Fail Alarm  
The Power Fail contact closure provides for an external LED indicator (lamp) or audible 
alarm upon loss of power.  
The indicator or audible alarm can be wired to operate as follows: 
•  ON when power is present 
•  ON when a power failure has occurred  
The Power Fail contact closure provides three contacts (terminals 1, 2 and 3) on terminal 
block TB2
 
Caution: 
Contact closure rated for 0.1 A @ 300 V maximum. 
» 
To connect the Power Fail contact closure: 
1. 
Remove the terminal block protective plastic cover. 
2. 
Wire a lamp or audible alarm to terminals 1, 2 or 3 on terminal block TB2 as follows 
(see figure): 
To enable the indicator when power is… 
Wire the lamp between… 
Present  
Terminals 1 and 2 
Absent 
Terminals 2 and 3 
For proper connection, the recommended tool torque settings for power terminal 
screws are 10.8 in-lb [1.22 Nm]. 
3. 
Replace the terminal block protective plastic cover. 
!