Analog Modules
5-40
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
5.7.1
Parameters of the Analog Input Modules
The analog input modules use a subset of the parameters and ranges of values
listed in the table below, depending on the functionality. Refer to the section on the
module concerned, starting from Section 5.18, to find out which subset the module
is capable of using.
The default settings apply if you have not performed parameter assignment in
STEP 7.
Table 5-42 Parameters of the Analog Input Modules 
Parameter
Value Range
Default
2)
Parameter
Type
Scope
Enable
Diagnostic interrupt
1)
Hardware interrupt
1)
Yes/no
Yes/no
No
No
Dynamic
Module
Destination CPU for
interrupt
1 to 4
Static
Module
Trigger for hardware
interrupt
End of scan cycle
reached at input
Yes/no
No
Static
Channel
High limit 
Low limit
Constraint possible due to measuring 
range
32511 to – 32512
– 32512 to 32511
Dynamic
Channel
Diagnostics   
Wire break  
Reference channel
error
Underflow
Overflow
Short circuit to M
Yes/no
Yes/no
Yes/no
Yes/no
Yes/no
No
No
No
No
No
Static
Channel