Analog Modules
5-59
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
5.13
Connecting Loads/Actuators to Analog Outputs
Introduction
You can use the analog output modules to supply loads and actuators with current
and voltage.
This section contains general information that is generally applicable to all the
connection options for loads and actuators described in the sections that follow.
Cables for Analog Signals
For
 
the
 
analog signals
you should
 
use
 
shielded
 
and
 
twisted
 
pair
 
 
cables. The cables
Q
V
 and S+ and M and S–, respectively, are to be twisted together.
 
This
 
reduces
 
the
interference
.  
Ground
 
the screen
 
of the analog cables at both ends of the cables.
If there are potential differences 
 
between 
 
the cable 
 
ends, an equipotential 
bonding 
 
current, which 
 
can flow 
 
over the 
 
shield, can 
 
cause interference of the
analog signals. In such a case, you should ground the shield at one end of the
cable only.
Isolated Analog Output Modules
With the isolated analog output modules there is no electrical connection between
the reference point of the measuring circuit M
ANA
 and chassis ground.
You must use isolated analog output modules if a potential difference U
ISO
 can
occur between the reference point of the measuring circuit M
ANA
 and chassis
ground. By means of an equipotential bonding conductor between the M
ANA
terminal and chassis ground, make sure that U
ISO
 does not exceed the permitted
value.