Siemens M7-400 Benutzerhandbuch
Analog Modules
5-117
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
A5E00069467-07
5.22.2
Measuring Methods and Measuring Ranges of the SM 431;
AI 16
AI 16
16 Bit
Measuring Methods
You can set the following measuring methods for the input channels:
•
Voltage measurement
•
Current measurement
•
Resistance test
•
Temperature measurement
You specify the setting by means of the measuring range modules on the module
and the “Measuring Type” parameter in STEP 7.
and the “Measuring Type” parameter in STEP 7.
Circuit Variants for the Channels
Two channels are set in each case with the measuring range module. There are
therefore restrictions as regards the measuring method for the adjacent channels
0/1, 2/3, 4/5, 6/7, 8/9, 10/11, 12/13 and 14/15, as shown in the following table:
therefore restrictions as regards the measuring method for the adjacent channels
0/1, 2/3, 4/5, 6/7, 8/9, 10/11, 12/13 and 14/15, as shown in the following table:
Table 5-66 Selection of the Measuring Method for Channel n and Channel n+1 of the SM 431;
AI 16
16 Bit
Meas. Type
Channel n+1
Channel n+1
Meas. Type
Channel n
Channel n
Disabled
Voltage
Current
4-DMU
Current
2-DMU
R-4L
R-3L
RTD-4L RTD-3L TC-L
Disabled
x
x
x
x
x
Voltage
x
x
x
Current four-wire
transmitter
transmitter
x
x
Current two-wire
transmitter
transmitter
x
x
Resistance
four-conductor
four-conductor
x
Resistance
three-conductor
three-conductor
x
Thermal resistor
four-conductor
four-conductor
x
Thermal resistor
three-conductor
three-conductor
x
Thermocouples
x
x
x