Siemens M7-400 Benutzerhandbuch

Seite von 638
Power Supply Modules
3-18
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
The following table applies to power supply modules with two batteries if the BATT
INDIC switch is in the 2BATT position. It shows the faults indicated and lists how to
remedy the faults.
Table 3-11
BAF, BATT1F, BATT2F; BATT INDIC LEDs on 2BATT
LED
Cause of Fault
Remedy
BAF
BATT1F
BATT2F
H
H
H
Both batteries are empty or
missing.
No backup voltage available
Insert new batteries in compartments 1
and 2
Press FMR momentary-contact
pushbutton
D
H
H
Both batteries empty or missing
Insert new batteries in compartments 1
and 2
Press FMR momentary-contact
pushbutton
H
H
D
Battery 1 empty or missing
Insert new battery in compartment 1.
Press FMR momentary-contact
pushbutton
No backup voltage available
(short circuit or overload)
Fault after plugging in a module:
Plugged-in module defective
Fault after switching on: Remove all
modules and plug in individually
D
H
D
Battery 1 empty or missing
Insert new battery in compartment 1.
Press FMR momentary-contact
pushbutton
Battery has been stored for too
long
Depassivate battery 
(see Installation Manual, Chapter 7)
H
D
H
Battery 2 empty or missing
Insert new battery in compartment 2.
Press FMR momentary-contact
pushbutton
No backup voltage available
(short-circuit or overload)
Fault after plugging in a module:
Plugged-in module defective
Fault after switching on: Remove all
modules and plug in individually
D
D
H
Battery 2 empty or missing
Insert new battery in compartment 2.
Press FMR momentary-contact
pushbutton
Battery has been stored for too
long
Depassivate battery 
(see Installation Manual, Chapter 7)
H
D
D
Both batteries in order.
No backup voltage available
(short circuit)
Fault after plugging in a module:
Plugged-in module defective
Fault after switching on: Remove all
modules and plug in individually
D
D
D
Both batteries in order.
D = LED is dark;  L = LED lights up;