Omron C200HE Benutzerhandbuch

Seite von 564
475
The “Operand” parameter indicates the data area where the SV is stored or a
constant. The “SV” parameter indicates the word address or the SV itself if it is a
constant.
Operand
Classification
Constant or
OP1
OP2
OP3
OP4
word address
C
I
O
(Space)
IR or SR
0000 to 0511
L
R
(Space)
(Space)
LR
0000 to 0063
H
R
(Space)
(Space)
HR
0000 to 0099
A
R
(Space)
(Space)
AR
0000 to 0027
D
M
(Space)
(Space)
DM
0000 to 6655
D
M
(Space)
DM (indirect)
0000 to 6655
C
O
N
(Space)
Constant
0000 to 9999
E
M
(Space)
(Space)
EM
0000 to 6143
E
M
(Space)
EM (indirect)
0000 to 6143
Limitations
The command is valid only when the UM setting is ladder only.
The command can’t be executed if the UM area is read-protected.
PC Settings
PC Mode
UM Area
RUN
MONITOR
PROGRAM
Write-protected
Read-protected
OK
OK
OK
OK
---
Execution Conditions
Commands
Responses
Single
Multiple
Single
Multiple
OK
---
OK
---
End Codes
An end code of 04 (address over) will be returned if the program address is
above the highest program address but less than 65,536 (32,767 in the
C200HS).
An end code of 14 (format error) will be returned if the length of the command is
incorrect.
An end code of 15 (entry number data error) will be returned if the program ad-
dress isn’t specified in BCD or the operand/SV parameters are incorrect.
An end code of 16 (command not supported) will be returned if the specified
instruction doesn’t exist in the program.
End code
Contents
00
Normal completion
04
Address over
13
FCS error
14
Format error
15
Entry number data error
16
Command not supported
18
Frame length error
23
User memory protected
Host Link Commands