MASTER LOCK LTR8-512M Benutzerhandbuch

Seite von 68
LTRx-512 Installation and User’s Guide 
Daylight Savings Codes 
30 
APPENDIX A - SPECIFICATIONS 
 
ELECTRICAL: 
Input Voltage   
 
 
120 or 220 / 240 VAC @ 60Hz or 50Hz 
Input Power 
 
 
 
50 VA max (less than 0.5A @ 120V) 
Memory / Quartz Time Backup  10 year (nom.) Lithium Battery 
Bell / Clock Control Relays 
 
120VAC / 28VDC, 10A , Pluggable 
Fuse 
 
 
 
 
1  x  1.0 Amp Main (AGC1) 
 
MECHANICAL / ENVIRONMENTAL: 
Operating Temperature 
32°-115° F  (0°-46° C) 
Weight 
About 12 lb. (depending on configuration) 
Dimensions 
See configuration drawings 
Mounting Options 
Semi-Flush, Surface, 19" Rack, Hidden Power Supply 
(some configurations optional) 
 
FUNCTIONAL: 
Secondary Clocks Supported 
Any two (2) of twenty-four (24) types plus Lathem 
DDC4R synchronization built-in; See Appendix B.  
One (1) of twenty-four (24) types plus Lathem DDC4R 
synchronization built-in; on the LTR4-512 
 
Bell Zones and Schedules 
Up to eight (8) zones [less two (2) for each electro-
mechanical secondary clock type]. {Up to four (4) zones 
on the LTR4-512.} 
 
Eight (8) Schedules, each allowing sixty-four (64) multi-
function events. 
 
Daylight Savings Time 
Supports DST standards for over 75 countries. See 
Appendix B. 
 
COMMUNICATIONS: (LTR8-512 and LTR8-512M) 
 
Remote Communications with 
RS-232 point-to-point @ 2400/9600 Baud 
Lathem LTR MasterLink, Terminal 
RS-485 multi-drop network  
Manager and “Atomic Clock” 
Internal modem (option) dial-in / dial-out 
 
Clock / Master Synchronization 
RS-485 Sync-In/Out Port @ 9600 Baud 
using DDC4R Protocols 
RS-485 Sync-Out Port @ 9600 Baud 
or Midnight Impulse 
Dry-contact input 
 
REGULATORY: 
Certifications / Registrations 
FCC Part15-ClassB, UL, cUL 
 
FCC Part 68 / Canada ICES-003 - Class B