PMCS 6.15 Envelope definition 
1) Physical System Size    
 
 
 
 
 
•  75 power management devices (IEDs) (100 max), 
•  150 I/O points (through IEDs or PLCs) 
•  64 ethernet serial communications ports, 
•  2 Modbus Monitors (maximum) using standard Modbus Monitor Proxy 
 
 
 
 
2) HMI Application Size -    
•  20,000 points/tags in HMI database (30K Max) 
•  600 HMI alarms configured max 
•  600 trended points (8 max per device) 
•  HMI I/O rates, alarm rates, and logging rates not to exceed 750 pts/sec 
•  13 HMI screens in CIMPLICITY utilizing Power Builder -10 device 
type and 50 user screens 
•  150 HMI screens in InTouch 
•  5 DDE ports in CIMPLICITY with no more than 10 devices 
configured per port 
•  10% of tags connected to enterprise solution 
•  Web-enabled only via CIMPLICITY WebView - no waveform or 
event viewers 
•  Maximum of one Viewer node 
3) Special Application Issues  
•  No redundancy  
•  Components to be run as NT services by default 
4) Performance  
 
 
 
                    
Response times:   
•  1 second or less to open an HMI screen 
•  1 seconds update time to populate a screen per device per serial 
port*(Except for UR Device) 
•  4 to 7 second time delay to display event in PMCS Event Viewer 
•  1 second response time to make device change (settings/ command 
coil) not including device feedback 
•  1000 device events/ sec burst support 
 
                     
Configuration: 
•  Maximum 15 devices per serial port 
•  Device baud rates set to maximum  
•  CIMPLICITY HMI points set for on-demand 
•  Devices supporting 125 register block reads 
•  Average CPU utilization <35% 
•  99% system uptime 
14  
  Getting Started 
CIMPLICITY PMCS Read-This-Book-First