Figure 23. 
Modbus Mode devices may be PLCs, RTUs, DCSs, or other Modbus devices, 
with links up to 32 nodes per Modbus network 
Connecting the Hardware 
With an RS-232 connection, the Zlinx 485 Base module is connected to a Modbus 
device via a DB-9M connector and an RS-232 cable. If the connected Modbus device is 
configured as a DTE device, use a straight-through cable. If the connected Modbus 
device is configured as a DCE device, use a null modem cable. 
Always check the interface specifications of the Modbus device to determine whether it is a DTE or 
DCE  before connecting. 
 
RS-232 may be connected to a PC using an RS-485 Converter, to allow using Modscan 32 to poll 
the registers.  
For RS-422/485 wiring, the Zlinx 485 Base module is connected to the Modbus device 
via the RS-422/485 terminal block. In RS-422/485 four-wire mode a cable containing 
two pairs and a ground/shield is used. In RS-485 two-wire mode a cable containing one 
pair and a ground/shield is used. 
Power is supplied to the converter via the power supply terminal block.