Siemens EN 50295 Benutzerhandbuch

Seite von 152
Siemens IK PI · 2004
6/116
AS-Interface Slaves
ECOFAST motor and soft starter
AS-Interface motor starters and IP65/67 load feeders
6
Overview
 
Distributed motor starters are used for switching and protecting 
loads locally. Versions with graded functional scope and with 
different installation possibilities ensure that both the functional 
requirements of the process and the constructional boundary 
conditions of the machine or installation are taken into account. 
Distributed motor starters are available for PROFIBUS DP and 
AS-Interface.
The starters can be installed in the vicinity of the motor or 
mounted onto the motor.
The following are available 
• Single units for geographically distributed motors and 
• Isolated solutions (ET 200X) for drives installed close together.
The functionality in the ECOFAST system ranges from direct on-
line starters, to reversing starters and soft starters through to 
frequency converters (ET 200X).
Brake contacts are available as an option for the starters. 
Two resp. four integrated digital contacts enable sensors to be 
scanned locally.
All starters are equipped throughout with standardized inter-
faces for data and power in accordance with the ECOFAST 
specification (DESINA compatible):
• HanBrid for PROFIBUS DP resp. insulation displacement 
method for AS-Interface
• Han Q8 for the power supply
• Han 10e for motor connection
The starters can be connected using T pieces for data and 
power to prevent interruption.
Selection and Ordering data 
 
Design
Order No.
Fieldbus 
interface
 
Switching 
function
 
Motor 
protection
 
Adjustment/
performance range
 
Brake 
output
 
PROFIBUS 
DP
Mechanical
Thermistor
0.3 to 9 A/4 kW
No
3RK1 303-2AS51-1AA0 
400 V AC
3RK1 303-2AS51-1AA3 
Thermal 
motor model
0.3 to 3 A/1.1 kW
No
3RK1 303-5BS41-1AA0 
400 V AC
3RK1 303-5BS41-1AA3 
2.4 to 9 A/4 kW
No
3RK1 303-5CS41-1AA0 
400 V AC
3RK1 303-5CS41-1AA3 
Electronic, soft
Full motor 
protection
0.3 to 3 A/1.1 kW
No
3RK1 303-6BS71-1AA0 
400 V AC
3RK1 303-6BS71-1AA3 
2.4 to 12 A/5.5 kW
No
3RK1 303-6DS71-1AA0 
400 V AC
3RK1 303-6DS71-1AA3 
electronic soft, 
several speeds, 
R255
0.6 to 4 A/1.5 kW
400 V AC
3RK1 303-6ES81-3AA3 
AS-Interface Mechanical
Thermistor
0.3 to 9 A/4 kW
No
3RK1 323-2AS51-1AA0 
400 V AC
3RK1 323-2AS51-1AA3 
Thermal 
motor model
0.3 to 3 A/1.1 kW
No
3RK1 323-5BS41-1AA0 
400 V AC
3RK1 323-5BS41-1AA3 
2.4 to 9 A/4 kW
No
3RK1 323-5CS41-1AA0 
400 V AC
3RK1 323-5CS41-1AA3 
Electronic, soft
Full motor 
protection
0.3 to 3 A/1.1 kW
No
3RK1 323-6BS71-1AA0 
400 V AC
3RK1 323-6BS71-1AA3 
2.4 to 12 A/5.5 kW
No
3RK1 323-6DS71-1AA0 
400 V AC
3RK1 323-6DS71-1AA3 
electronic soft, 
several speeds, 
R255
0.6 to 4 A/1.5 kW
400 V AC
3RK1 323-6ES81-3AA3 
Micro Starter 
mechanical
Thermistor
0.3 to 9 A/4 kW
No
see Catalog M11