AS-Interface Slaves
AS-Interface customized enclosures 
and front panel modules
SIGNUM pushbuttons and indicator lights
6
Overview
Customized solutions for linking command devices to 
AS-Interface permit the configuration of command devices to be 
selected as required. In addition to the enclosures, the AS-Inter-
face front panel module provides a solution for SIGNUM 3SB3 
Command Devices mounted in front panels.
 
AS-Interface front panel module
 
AS-Interface enclosure
Design
AS-Interface enclosure
The enclosures with two, three, four and six command points are 
equipped with a 4I/4O slave. Up to four inputs (switch contacts) 
and four outputs (lamp holders) can therefore be connected to 
them. A second slave can be mounted on enclosures for four 
and six command points. Addressing is via the AS-Interface 
connections or via the built-in addressing socket. An external 
supply voltage is not required. 
For enclosures with EMERGENCY STOP, the EMERGENCY 
STOP actuator can be wired conventionally or alternatively using 
the AS-Interface F adaptor.
With conventional wiring, interrogation can be performed via AS-
Interface. In this case, a second slave cannot be mounted on the 
enclosure for four command points.
In the case of conventional wiring of the EMERGENCY STOP, up 
to three switch contacts can be selected for the EMERGENCY 
STOP; if the EMERGENCY STOP is scanned via AS-Interface, 
two contacts are possible.
If the EMERGENCY STOP is wired via the F adaptor, the safe 
module is mounted above or to the right. The AS-Interface cable 
is then looped through to supply the non-safe command devices 
of the enclosure. EMERGENCY STOP via an F adaptor is only 
possible for enclosures for three, four or six command points.
The following methods can be used for connecting the AS-Inter-
face cable:
• Terminal for shaped AS-Interface cable. Contact is made with 
the cable using the insulation piercing method and it is routed 
externally past the enclosure.
• Cable gland for the shaped AS-Interface cable or round cable. 
The cable is inserted into the enclosure.
• Connection via M12 connectors
• In the case of enclosures with EMERGENCY-STOP via the AS-
Interface F adaptor, the cable is connected using the terminals 
mounted on the F adaptor for the shaped AS-Interface cable. 
The cable is routed externally past the enclosure.
 
Typical connections
If not all the inputs and outputs of the slave built into an enclo-
sure are used, the spare inputs and outputs can be routed to the 
outside via an M12 socket at the top and bottom of the enclo-
sure. The pin assignment required for the M12 socket must then 
be specified on the order supplement (see section Options). 
N
S
D
0_
00
05
3a
A S - I n t e r f a c e   c a b l e
T e r m i n a l
F r o n t   p a n e l   m o d u l e
N
S
D
0
_
0
0
0
5
8
T e r m
i n a l
S h a p e d
A S - I n t e r f a c e   c a b l e
F l e x i b l e   l e a d
( a p p r o x .
2 0   c m   l o n g )
E n c l o s u r e   p a r t
E n c l o s u r e
c o v e r
P C B
N
S
A
0
_
0
0
3
4
6
A S - I n t e r f a c e   c a b l e   i s
r o u t e d   e x t e r n a l l y   a l o n g -
s i d e
T h e   A S - I n t e r f a c e   c a b l e
i s   l a i d   i n   t h e   m o d u l e
R o u n d   c a b l e   i s   l a i d   i n
t h e   m o d u l e