Siemens EN 50295 Benutzerhandbuch

Seite von 152
Siemens IK PI · 2004
6/143
AS-Interface
Transmission media
AS-Interface shaped cable
6
Overview
The actuator-sensor interface, the networking system for the low-
est field level, is characterized by easy assembly and installa-
tion. A new connection technique has been specially developed 
for the AS-Interface.
The network stations are interconnected via the the AS-Interface 
cable. This two-core cable has a trapezoidal profile which pre-
vents polarity reversal.
Connection is made with the cable using the insulation penetra-
tion technique. Blade contacts penetrate the AS-Interface 
shaped cable and make reliable contact with the two cores. 
Cutting and stripping of cores is not necessary. This technique 
allows AS-Interface stations (e.g. I/O modules, intelligent de-
vices) to be connected in the shortest possible time. Devices 
can also be replaced in an instant.
The AS-Interface cable is offered in various materials (rubber, 
TPE, PUR) to suit applications in a wide range of environmental 
conditions (e.g. in an atmosphere saturated with oil particles).
It is also possible to use a round cable for special applications. 
In the case of AS-Interface, data and a 24 V DC auxiliary supply 
voltage can be connected for the sensors (e.g. BERO proximity 
switches) and actuators (e.g. LEDs) via the yellow AS-Interface 
cable. 
For 24 V DC actuators (e.g. solenoid valves) that have a high 
current requirement or that are integrated into EMERGENCY 
STOP circuits, the black AS-Interface cable must be used.
Technical specifications
 
EPDM 
(rubber) 
TPE 
(special PVC compound) 
TPE special version 
acc. to UL Class 2 
PUR 
(Polyurethane) 
Operating temperature range
• Stationary in °C
-40 to +85
-40 to +105
-30 to + 90
-50 to +90
• Moving in °C
-25 to +85
-30 to +105
-20 to + 90
-50 to +90
Color of cores
Brown, blue
Brown, blue
Brown, blue
Brown, blue
Flexibility
Very Good
Good
Good
Good
Behavior in fire
flammable
flame-retardant acc. to
IEC 60332-1
VDE 0482 T. 265-2-1
UL 1581 sec. 1061 cable 
flame
UL 1581 sec. 1060 CSA 
FT1
flame-retardant acc. to
IEC 60332-1
VDE 0482 T. 265-2-1
UL 1581 sec. 1061 cable 
flame
UL 1685 CSA FT4
flame-retardant acc. to
IEC 60332-1
VDE 0482 T. 265-2-1
Halogen-free (PVC-free)
Yes
No
No
Yes
Silicone emission free
Yes
Yes
Yes
Yes
Ozone and weather resistant
Conditionally resisting
Resisting
Resisting
Resisting
Oil resistance
Conditionally resisting
Resisting
Resisting
Resisting
Smallest permissible bending 
radius acc. to DIN VDE 0298, 
Part 300, in mm 
• Fixed in place
12
12
12
12
• Flexible
24
24
24
24
$6,QWHUIDFH