AS-Interface
Introduction
Technical specifications
6
Technical specifications
 
More information
Please note the operating framework conditions in each case for 
the specified SIMATIC NET products (Order No. 6GK..., 6XV1...), 
which you will find on the Internet page listed below.
Additional information is available in the Internet under:
http://www.siemens.de/simatic-net/ik-info
Standard
EN 50295
Topology
Bus, star or tree topology 
(like electrical installation)
Transmission medium
Unshielded two-wire cable 
(2 x 1.5 mm
2
) for data and 
auxiliary power
Connection method
Contacting of the AS-Interface 
cable using the insulation 
displacement method
Permissible cable length max.
100 m w/o repeater/extender
500 m range with repeater/
extender (parallel connection 
of repeaters)
Cycle time max.
5 ms with full expansion,
10 ms using A/B method
Number of stations max.
31 slaves accord. to Complete 
AS-Interface Spec. V2.0 ;
62 slaves accord. to Complete 
AS-Interface Spec. V2.1 
(A/B method),
integrated analog value 
transmission
Number of binary 
sensors/actuators
Max. 124 I/124 O
modules according to spec. V2.0;
Max. 248 I/186 O
modules according to spec. V2.1
Access procedure
Cyclical master-slave polling 
method, cyclical acceptance 
by host (PLC, PC)
Error correction
Identification and repetition of 
faulty messages