AS-Interface Slaves
I/O modules for operation in the field
Analog I/O modules IP67 - K60
6
Overview
 
The two-channel modules in the K60 compact series collect or 
supply analog signals locally. These modules are linked to a 
higher-level programmable controller via an AS-Interface master 
acc. to Specification 2.1.
The analog modules are grouped into five categories:
• Input module for two current sensors
• Input module for two voltage sensors
• Input module for two temperature sensors
• Output module for two current actuators
• Output module for two voltage actuators
The input and output channels are galvanically isolated from the 
AS-Interface network. If sensors with a greater power consump-
tion are to be connected, instead of the internal supply, more 
power can be supplied via the auxiliary voltage.
The modules, complete with their technical specifications and 
detailed operating instructions, are presented in the manual in 
considerable detail. This is supplemented with function block 
examples.
Function
Data transfer in accordance with the 7.3/7.4 analog profile (simplified)
In the case of the 7.3/7.4 analog profile, at least seven AS-Inter-
face cycles are executed until data transfer is complete. For this 
purpose, a master with the expanded specification V2.1 
must be used.
In the case of input modules, the complete analog value is then 
available in the AS-Interface master. Preprocessing takes place 
in the master. 
The user program fetches the analog value as one value into the 
user program on the next system function call. The analog value 
is therefore updated extremely quickly. 
This procedure takes place in reverse order in the case of output 
modules.
Technical specifications
 
NSA0_00352a
A n a l o g
m o d u l e
A S -
I n t e r f a c e
m a s t e r
C P U
O n e   u s e r   p r o g r a m   c y c l e ,
w i t h   s y s t e m   f u n c t i o n   c a l l
S e v e n   A S -
I n t e r f a c e   c y c l e s
( m a x .   5   m s   e a c h )
N o t e :   T h e   i n t e g r a t e d   s t a n d a r d   f u n c t i o n   b l o c k s   S F C 5 8 ,   S F C 5 9
c a n   b e   u s e d   f o r   a c c e s s   t o   t h e   v a l u e s .
Slave type
Analog-Slave
Profile
7.3
Numerical format
S7
Operational voltage in accordance  
with AS-Interface specification in V  
26.5 to 31.6
Total current consumption of the 
module including the connection 
of sensors/actuators in mA
150
Current drawn with two sensors 
connected in mA 
(without U
Aux
 infeed)
Max. 46
Additional supply of sensors 
via U
Aux
 in V
24 to 30
Current drawn from U
Aux
 on 
connection of 2 sensors 
(not short-circuit-proof) in mA
Max. 500
Current drawn on connection of 2 
current / voltage actuators in mA
Max. 30 / max. 24
I/O configuration
7
ID code
3
AS-Interface certificate
In preparation
Approvals
UL/CSA/ship building
Degree of protection
IP67 
Ambient temperature in °C
-20 to +60
Storage temperature in °C
-40 to +85
AUX PWR display (U
Aux
)
Green LED
AS-i display
Green LED
FAULT display
Red LED
Connection
Mounting plate for K60 compact 
module