Siemens 2000592-001 Benutzerhandbuch
Command Descriptions,
Continued
reset
This command resets and saves the configuration parameters in non-
volatile memory.
volatile memory.
test
This command places a selected port into a hardware diagnostic mode.
The test mode can be used to verify cable continuity and DataNET signal
levels when used in conjunction with an Oscilloscope or other test
device.
The test mode can be used to verify cable continuity and DataNET signal
levels when used in conjunction with an Oscilloscope or other test
device.
The command:
test 1
places port 1 into test mode. The device will generate poll messages on
port 1 every 50 milliseconds. The other port continues to operate
normally. The command:
port 1 every 50 milliseconds. The other port continues to operate
normally. The command:
test off
turns off test mode. Only one port at a time may be in test mode.
timeout
This command may be used to disable the user login timeout. Normally,
if a user has not issued a CLI command for five minutes, the device will
automatically shut down the user’s login session. This command may be
used to defeat (and re-enable) this timeout:
if a user has not issued a CLI command for five minutes, the device will
automatically shut down the user’s login session. This command may be
used to defeat (and re-enable) this timeout:
timeout off
Disables timeout. The device will not automatically
log out the user; regardless of the time elapsed since
the user last issued a CLI command.
log out the user; regardless of the time elapsed since
the user last issued a CLI command.
timeout on
Re-enables the five-minute CLI timer.
44
• Command Summary
2000592-001